KGL Operating Manual – VS 3010 BS
2018-07-02
/
145 178
Var. load time F ID: XXXXX
Input
Default
Dim.
Vas Load T C8 XXX s
3..250
250
sec.
Base module: 1 – max. 4 capacity stages
with first SIOX extension module: 1 – max. 8 capacity stages
Screen 3-2-1-6-c Basic time capacity stage OFF
B. UNLO T ID: XXXXX
Input
Default
Dim.
B. UNLO T C1 XXX s
Only the available capacity stages are displayed.
3..250
5
sec.
B. UNLO T C2 XXX s
3..250
10
sec.
...
B. UNLO T C8 XXX s
3..250
30
sec.
Base module: 1 – max. 4 capacity stages
with first SIOX extension module: 1 – max. 8 capacity stages
Screen 3-2-1-6-d Variable time capacity stage OFF
V. UNLO T ID: XXXXX
Input
Default
Dim.
V. UNLO T C1 XXX s
Only the available capacity stages are displayed.
3..250
20
sec.
V. UNLO T C2 XXX s
3..250
40
sec.
...
V. UNLO T C8 XXX s
3..250
80
sec.
Base module: 1 – max. 4 capacity stages
with first SIOX extension module: 1 – max. 8 capacity stages
Menu 3-2-1-7 LP control Day Z2
LP CONT D ID:
XXXXX
Input
Default
Dim.
to-Max. Z2 XXX °C
max. t -setpoint for setpoint shift
0
-50..
10
-34
°C
tr_Min. Z2 XXX °C
minimum room temperature for setpoint shift (only visible if t -adjustment via room temperature -
0
screen 3-2-2-a)
-25..
20
15
°C
to-Min. Z2 XXX °C
min. t -setpoint for setpoint shift
0
-50..
10
-38
°C
tr-Max. Z2 XXX °C
max. room temperature for setpoint shift (only visible if t -adjustment via room temperature -
0
screen 3-2-2-a)
-18..
35
25
°C
humid. adapt X
Humidity shift activated YES/NO
Y/N
N
-
Bas. load time F →
Display basic times tb ON
→
Screen 3-2-1-7-
a
Var. load time F →
Display of the variable times tv ON
→
Screen 3-2-1-7-
b
Bas.unload time F
→
Display basic times tb OFF
→
Screen 3-2-1-7-
c
Var.unload time F
→
Display of the variable times tv OFF
→
Screen 3-2-1-7-
d
Neutral Zone XX K
Switching hysteresis for step control
1..10
4
K
Control const. XX K
Max. control error for variable control times
1..15
7
K
Screen 3-2-1-7-a Basic time capacity stage ON