KGL Operating Manual – VS 3010 BS
2018-07-02
/
109 178
Warning about dangerous electrical voltage! Danger of electric shock! BEFORE connecting and
disconnecting, it must be ensured that
is present at all connections of the controller.
no voltage
Wiring of the digital inputs: all digital inputs must be set to 230 V AC for the operation.
If 230 V AC is applied to an input that has been configured for 24 V AC, this results in destruction of
the control component.
Terminal No.
Function
Base module
SIOX 1
50, 51
-
High-pressure cutout
52, 53
-
LP cutout Z1
54, 55
58, 59
62, 63
66, 67
-
Oil differential pressure / HP switch for compressor 1 *
Oil differential pressure / HP switch for compressor 2 *
Oil differential pressure / HP switch for compressor 3 *
Oil differential pressure / HP switch for compressor 4 *
-
50, 51
54, 55
58, 59
62, 63
Oil differential pressure / HP switch for compressor 5 *
Oil differential pressure / HP switch for compressor 6 *
Oil differential pressure / HP switch for compressor 7 *
Oil differential pressure / HP switch for compressor 8 *
* Digital inputs configurable as:
oil differential pressure switch for compressor or
HP cutout for compressor or
oil differential pressure / HP switch for compressor
Terminal No.
Function
Base module
SIOX 1
56, 57
60, 61
64, 65
68, 69
-
Motor overload cutout, compressor 1
Motor overload cutout, compressor 2
Motor overload cutout, compressor 3
Motor overload cutout, compressor 4
-
52, 53
56, 57
60, 61
64, 65
Motor overload cutout, compressor 5
Motor overload cutout, compressor 6
Motor overload cutout, compressor 7
Motor overload cutout, compressor 8
70, 71
72, 73
74, 75
76, 77
-
Motor overload cutout, condenser 1
Motor overload cutout, condenser 2
Motor overload cutout, condenser 3
Motor overload cutout, condenser 4 *
-
66, 67
68, 69
70, 71
72, 73
Motor overload cutout, condenser 5
Motor overload cutout, condenser 6
Motor overload cutout, condenser 7
Motor overload cutout, condenser 8 *
78, 79
-
External alarm
or
speed controller error with activated compressor combined control
80, 81
-
Fast unload - external OFF
82, 83
84, 85
-
Load shedding Z1 stage 1
Load shedding Z1 stage 2
86, 87
-
Load shedding Z2
88, 89
-
Setpoint toggle (daytime / night operation)
90, 91
-
LP cutout Z2