KGL Operating Manual – VS 3010 BS
2018-07-02
/
111 178
Warning about dangerous electrical voltage! Danger of electric shock! BEFORE connecting and
disconnecting, it must be checked that
at the 230 V AC relay outputs! Low
no voltage is present
voltage
extra-low voltage must
be applied at the relay outputs!
and
not
Terminal No.
Function
Base module
SIOX 1
1, 2
Consumer enable Z1
or
base load rotation FC Z1
or
enable E-valve 1 cascade
3, 4
Consumer enable Z2
or
base load rotation FC Z2
or
enable E-valve 1 cascade
13, 14
23, 24
33, 34
43, 44
-
Compressor 1* control
Compressor 2 control
Compressor 3 control
Compressor 4 control
-
13, 14
23, 24
33, 3443, 44
Compressor 5 control
Compressor 6 control
Compressor 7 control
Compressor 8 control
Terminal No.
Function
Base module
SIOX 1
15,16, 18
25, 26, 28
-
Condenser fan 1 control
Condenser fan 2 control
35, 36, 38
-
Condenser fan 3 control
or
enable E-valve 1 cascade
45, 46, 48
-
Condenser fan 4 control
or
enable E-valve 2 cascade
-
15,16, 18
25, 26, 28
Condenser fan 5 control
Condenser fan 6 control
35, 36, 38
Condenser fan 7 control
or
enable E-valve 1 cascade
45, 46, 48
Condenser fan 8 control
or
enable E-valve 2 cascade
* Special features for the relay outputs for control of the fans:
* When compressor combined control is activated, the enable of the FC compressor for Z1 or Z2 is
always performed via the relay output “compressor controller” of the first compressor in the circuit Z1
or Z2. This means that the enable of the FC compressor Z1 is always performed using the
compressor 1 controller relay contact.
For Z2, this means that, e.g. in the case of a compressor configuration Z1 with
, the
4 compressors
compressor 5 relay contact is used for the enable of the FC compressor Z2.