This fault report is active when there is no voltage at the external alarm / speed controller input, i.e.
the external alarm / speed controller must be configured and connected so that 230 V AC is present
at the input 15 of the pack controller in the good state.
B. Fan combined control
An additional digital input is always required for the monitoring of the FC / speed controller for fan combined
control. The input "Motor protection fan" is used which always follows the last used motor protection input. For
this control mode, the message text for this input is automatically set to
.
Speed controller HP
Example:
Number of fans n = 3
Number (n) of the digital inputs for motor protection fan = 3: M1 ... M3
Digital input for monitoring the FC / speed controller (n+1): 4th input (M4)
The fault report is active when there is no voltage at the "Motor protection fan" (n+1) input, i.e. the FC
/ speed controller must be configured and connected so that 230 V AC is applied to this pack
controller input in the good state.