KGL Operating Manual – VS 3010 BS
2018-07-02
/
155 178
Messages ID:
XXXXX
Input
Default
Dim.
Meas. error R5.1
X
-, 0..
99
Meas. error R6.1
X
Measuring circuit fault in evaporator outlet temperature sensor R6.1
-, 0..
99
2
-
check OD X
A controller state has been reached where the opening degree takes on implausible values.
-, 0..
99
1
-
manual OD X
The control function has been disabled. The opening degree is set manually.
-, 0..
99
0
-
HP EMERG.-
OFF Z1
The EMERGENCY OFF threshold for the Z1 high-pressure has been exceeded and all compressor
stages have been shut down immediately.
-, 0..
99
2
-
HP EMERG.-
OFF Z2
The EMERGENCY OFF threshold for the Z2 high-pressure has been exceeded and all compressor
stages have been shut down immediately.
-, 0..
99
2
-
Menu 3-8-3 D2D Discharge gas defrosting *
* Discharge gas defrosting only when this has also been activated, see chapter
Default settings with S1, page
.
D2D ID: XXXXX
Input
Default
Dim.
Defrost →
Type of defrosting
or
Z2 and Z2
Only Z1 defrost
→
Screen 3-8-a
Def. Z2R →
Z2 rooms type of defrosting
→
Screen 3-8-b
Defrost timer →
Defrost times entry screen
→
Screen 3-8-c
Def.timer Z2-R
→
Z2R defrost times entry screen for separate defrost (only visible if
or
is
Auxiliary defrost
Separate
selected in screen 3-8-b)
→
Screen 3-8-d
tc Comp OFF
XX°C
Z1 capacity stages will be unloaded above the entered temperatures
30..40
35
°C
tc comp. DIS XX°
C
No Z1 capacity stages will be loaded above the entered temperatures
20..30
25
°C
Drain htr. Z2
XXm
Z2 cold rooms defrost heater lead time
5..30
15
Min.
Defrost Z2 XXm
Z2 cases defrost duration
10..30
12
Min.
Comp. OFF Z2 X
Disabling of z2 compressors during defrost YES/NO
↑, ↓, (Y
/N)
Y
-
C.Suct.l.on Z2
XX°C
After Z2 defrost, Z2 compressors remain disabled until this temperature is reached
-10..5
-5
°C
to-Setpt Z1 X°C
t -setpoint Z1 during discharge gas defrosting for joint Z2 and Z2R defrost
0
-30..-5
-20
°C
Bas.Load t. Z1
XXs
Z1 basic load time during D2D Z2
5..200
20
sec.
Bas.unlo t. Z1
XXs
Z1 basic unload time during D2D Z2
5..100
10
sec.
Defrost Z2R
XXm
Z2 rooms defrost duration
10..30
10
Min.
Del.Z1 Def. XXm
Z1 defrost delay after Z2 defrost
0..90
5
Min.
Defrost Z1 XXm
Z1 cases defrost duration
10..30
20
Min.
to-Setpt Z2 X°C
t -setpoint Z2 during discharge gas defrosting Z1
0
-50..-20
-38
°C
Bas.Load t. Z2
XXs
Z2 basic load time during D2D Z1
5..200
20
sec.
Bas.unlo t. Z2
XXs
Z2 basic unload time during D2D Z1
5..100
10
sec.
Menu 3-8 D2D Discharge gas defrosting *