CHAPTER 8 - PXG600E CONFIGURATION WEB PAGE
49
EATON
PXG600E User Manual • IM02603003E
Rev 5, 11-May-2012 • Firmware Version 5.03:3835
BACnet/IP
BACnet/IP communication provides read-only data from Building
Automation Systems (BASs), so that the PXG600E can be easily integrated in
a BAS alongside other BACnet/IP-capable devices.
Initial Setup
1.
Click on the
BACnet/IP
link
(Figure 38, A)
in the toolbar of the PXG600E
configuration web page.
2.
The initial setup screen requires that you first set a
Routed Network
Number
(Figure 38, B)
. Each BACnet/IP network uses the Routed
Network Number to identify it. Ask your network administrator for the
routed network number for the BACnet/IP network you wish to connect
to. Accepted values are 1 to 65536.
Figure 38
3.
Click SAVE ALL SETTINGS
(Figure 38, C)
.
4.
Wait 10-30 seconds and then click the
Refresh
link
(Figure 38, D)
.
5.
The following WARNING message
(Figure 39, A)
appears, click OK
(Figure 39, B)
.
Figure 39