CHAPTER 10 - PXG600E WEB PAGES
167
EATON
PXG600E User Manual • IM02603003E
Rev 5, 11-May-2012 • Firmware Version 5.03:3835
Waveforms
The PXG600E supports waveform acquisition for selected devices capable of
generating waveforms. This feature is user-selectable on the device
configuration page. The waveform files are converted and stored as a
COMTRADE file format. The files can then be downloaded and viewed using
a standard COMTRADE waveform viewer. Please refer to the device data
map at
www.eaton.com/pxg
for the list of devices that support this
feature.
Procedure to Download a Waveform
Use the following procedure to download a data log.
1.
Click on the WAVEFORMS
(Figure 183, A)
button.
2.
Click on the download symbol
(Figure 183, B)
to download the
waveform file.
NOTICE: The file you download will have the format “*.tgz”
where “*” is a wildcard. This file is compressed and must be
extracted with a program such as WinZip
®
. The *.tgz” file
contains three files: “*.hdr,” “*.dat” and “*.cfg.” You MUST use
a third party COMTRADE waveform viewer to view these
waveform files.
3.
Click on the delete symbol
(Figure 183, C)
to delete the
waveform file.
Figure 183
NOTICE: The Modbus communications device handler is not
capable of generating waveforms. This affects products like the
FP5000 and FP6000 Feeder Protector Modbus versions.
NOTICE: The time displayed in the waveform timestamp is
expressed in GMT.
B
C
A
PXG600E_185