UPS INSTALLATION PLAN AND UNPACKING
Power Xpert
9395 UPS (450–550 kVA) Installation and Operation Manual
164201701 Rev 3
www.eaton.com/powerquality
3-13
Table 3‐9. Supplied Terminal Hardware Kit
Part
Size
Quantity
Terminals Used On
Eaton Part Number
Bolt, Grade 5
M10 x 30 mm
23
Ground and Neutral
180190078-088
Bolt, Grade 5
M12 x 45 mm
52
Rectifier Input, Bypass Input,
Battery Input, and Output
180190078-113
Flat Washer
M10
23
Ground and Neutral
180500036-100
Flat Washer
M12
104
Rectifier Input, Bypass Input,
Battery Input, and Output
180500036-120
Conical Washer
M10
23
Ground and Neutral
180500037-100
Conical Washer
M12
52
Rectifier Input, Bypass Input,
Battery Input, and Output
180500037-120
Nut
M12
52
Rectifier Input, Bypass Input,
Battery Input, and Output
180200001-07
NOTE
Bypass terminations are not applicable to IOM configurations.
Table 3‐10. Recommended Installation Parts and Tools (Not Supplied by Eaton
)
Part
Size
Quantity
Manufacturer
Part Number
Notes
Long Barrel 2‐Hole Lug
2/0 AWG
As required
Thomas & Betts
54862BE
Copper wire only
3/0 AWG
Thomas & Betts
54864BE
4/0 AWG
Thomas & Betts
54866BE
250 MCM
Thomas & Betts
54868BE
300 MCM
Thomas & Betts
54870BE
350 MCM
Thomas & Betts
54872BE
400 MCM
Thomas & Betts
54874BE
500 MCM
Thomas & Betts
54876BE
Manual Hydraulic Crimp Tool
14 Ton
1
Thomas & Betts
TBM14M
Die Set
N/A
1
Thomas & Betts
15506
Table 3‐11. Separate Rectifier Input UPM Power Cable Terminations for the 9395-550/450, 9395-550/500, and 9395-550/550
Terminal Function
Terminal
Function
Size of Pressure Termination
Tightening Torque
Nm (lb ft)
Type Screw
AC Input to each UPM Rectifier
E1
Phase A
2 - #6-250 kcmil
42.4 (375)
5/16
”
Hex
E2
Phase B
2 - #6-250 kcmil
42.4 (375)
5/16
”
Hex
E3
Phase C
2 - #6-250 kcmil
42.4 (375)
5/16
”
Hex