background image

9390

INSTALLATION & OPERATION MANUAL

UPS

40–80 kVA

www.powerware.com

Содержание 9390

Страница 1: ...9390 INSTALLATION OPERATION MANUAL UPS 40 80 kVA www powerware com ...

Страница 2: ...ipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense WARNING This is a product for restr...

Страница 3: ...packing the UPS Cabinet 2 2 3 Installing the UPS System 3 1 3 1 Preliminary Installation Information 3 1 3 2 UPS Cabinet Installation 3 1 3 2 1 Unloading the Powerware 9390 UPS Cabinet from the Pallet 3 1 3 2 2 Battery Cabinet Installation 3 5 3 2 3 Installing UPS External and Battery Power Wiring 3 5 3 2 4 Installing Interface Connections 3 7 3 2 4 1 TB1 Connections 3 7 3 2 4 2 TB2 Connections 3 ...

Страница 4: ...S Standard Features 7 1 7 1 1 Control Panel 7 1 7 1 2 Customer Interface 7 1 7 1 2 1 Building Alarm Monitoring 7 1 7 1 2 2 Alarm Contact 7 1 7 1 3 X Slot Communication Bay 7 1 7 1 4 Advanced Battery Management 7 1 7 1 5 LanSafe Power Management Software 7 1 7 1 6 Installation Features 7 2 7 2 Options and Accessories 7 2 7 2 1 Battery Cabinets 7 2 7 2 2 Optional X Slot Cards 7 2 7 3 Symbols Control...

Страница 5: ...trol 9 5 9 9 Using the LOAD OFF Pushbutton 9 6 9 10 Using the Remote Emergency Power Off Switch 9 7 10 Using Features and Options 10 1 10 1 Building Alarm Monitoring 10 1 10 2 General Purpose Relay Contact 10 1 11 Responding to System Events 11 1 11 1 General 11 1 11 2 System Event Horns 11 1 11 3 System Event Indicators 11 1 11 4 System Event Messages 11 1 12 Communication 12 1 12 1 X Slot Cards ...

Страница 6: ...L Maintenance 13 3 13 2 4 BATTERY Maintenance 13 3 13 3 Maintenance Training 13 3 14 Product Specifications 14 1 14 1 Model Numbers 14 1 14 2 UPS System Input 14 1 14 3 UPS System Output 14 2 14 4 Environmental Specifications 14 2 14 5 Battery Specifications 14 3 Appendix A Installation Information A 1 Warranty W 1 ...

Страница 7: ...8 4 Active Events Screen 8 4 Figure 8 5 History Screen 8 5 Figure 8 6 Output Meter Screen 8 6 Figure 8 7 Input Meter Screen 8 7 Figure 8 8 Bypass Meter Screen 8 7 Figure 8 9 Battery Meter Screen 8 8 Figure 8 10 Output Current Load Meter Screen 8 8 Figure 8 11 System Setup Level 0 Screen 8 9 Figure 8 12 Contrast Adjust Screen 8 10 Figure 8 13 Versions Screen 8 11 Figure 8 14 Unit Type Screen 8 11 F...

Страница 8: ...Table of Contents vi Powerware 9390 UPS 40 80 kVA Installation and Operation Manual S 164201535 Rev A This page intentionally left blank ...

Страница 9: ...e to unexpected power problems The Powerware 9390 UPS continually monitors incoming electrical power and removes the surges spikes sags and other irregularities that are inherent in commercial utility power Working with a building s electrical system the UPS system supplies clean consistent power that sensitive electronic equipment requires for reliable operation During brownouts blackouts and oth...

Страница 10: ... This manual uses these type conventions 쑺 Bold type represents a command or option that you type or enter at a prompt 쑺 Italic type highlights notes and new terms where they are defined 쑺 Screen type represents information that appears on the screen or LCD Icon Description Information notes call attention to important features or instructions Keys Brackets are used when referring to a specific ke...

Страница 11: ... a temperature and humidity controlled indoor environment free of conductive contaminants Ambient temperature must not exceed 40 C 104 F Do not operate near water or excessive humidity 95 max The system is not intended for outdoor use 쑺 Ensure all power is disconnected before performing installation or service C A U T I O N 쑺 Batteries can present a risk of electrical shock or burn from high short...

Страница 12: ... illustrations of the cabinet including dimension and connection point drawings Visit www powerware com or contact your Powerware service representative for information on how to obtain copies of this manual 1 5 Getting Help If help is needed with any of the following 쑺 Scheduling initial startup 쑺 Regional locations and telephone numbers 쑺 A question about any of the information in this manual 쑺 ...

Страница 13: ...1 1 Powerware 9390 UPS 40 80 kVA Installation and Operation Manual S 164201535 Rev A Section I Installation ...

Страница 14: ...1 2 Powerware 9390 UPS 40 80 kVA Installation and Operation Manual S 164201535 Rev A This page intentionally left blank ...

Страница 15: ...ek notice is required to reserve a preferred startup date 2 1 Creating an Installation Plan Before installing the UPS system read and understand how this manual applies to the system being installed Use the procedures and illustrations in the following chapters to create a logical plan for installing the system 2 2 Preparing the Site For the UPS system to operate at peak efficiency the installatio...

Страница 16: ... including the minimum AWG size of external wiring see Table E on page A 7 The power wiring connections for this equipment are rated at 90 C If wire is run in an ambient temperature greater than 30 C higher temperature wire and or larger size wire may be necessary Control wiring for Emergency Power Off and optional accessories such as building alarms and monitoring interface should be connected at...

Страница 17: ...age during transit C A U T I O N Do not install a damaged cabinet Report any damage to the carrier and contact your Powerware service representative immediately 2 Use a forklift or pallet jack to move the packaged cabinet to the installation site or as close as possible before unpacking Insert the forklift or pallet jack s forks between the pallet supports on the bottom of the unit NOTE Verify tha...

Страница 18: ...he protective covering from the cabinet 5 Remove the packing material and discard or recycle them in a responsible manner 6 After removing the protective covering inspect the contents for any evidence of physical damage and compare each item with the Bill of Lading If damage has occurred or shortages are evident contact your Powerware service representative immediately to determine the extent of t...

Страница 19: ...pment 쑺 If perforated floor tiles are required for ventilation place them in front of the UPS See Table A on page A 3 for equipment weight and point loading 쑺 Details about control wiring are provided in each procedure for connecting options and features Drawing 164201535 8 and Table M through Table P starting on page A 19 identify the control wiring terminations 3 2 UPS Cabinet Installation To in...

Страница 20: ... the pallet Remove the front ant ship shipping bracket Retain front anti tip shipping bracket and securing hardware for later use Do not discard front anti tip shipping bracket This bracket is required for installation 6 Remove three bolts 4 in Figure 3 2 securing removable skid 5 and remove skid NOTE In the following step the pallet will tilt and act as a ramp once the cabinet is rolled beyond th...

Страница 21: ...201535 Rev A SHIPPING BOLTS 1 FRONT VIEW PALLET VENTED FRONT DOOR FRONT ANTI TIP SHIPPING BRACKET 3 NOTE WIDER BASE SHIPPING BOLTS 2 NOTE DO NOT DISCARD THE FRONT ANTI TIP SHIPPING BRACKET THIS BRACKET IS REQUIRED FOR INSTALLATION Figure 3 1 Removing Front Shipping Bracket on the Powerware 9390 UPS ...

Страница 22: ...UPS 40 80 kVA Installation and Operation Manual S 164201535 Rev A REAR SHIPPING BRACKET 3 PALLET SKID BOLTS 4 3 PLACES REMOVABLE SKID 5 REAR VIEW SHIPPING BOLTS 1 SHIPPING BOLTS 2 Figure 3 2 Removing Rear Shipping Bracket on the Powerware 9390 UPS ...

Страница 23: ...stallation To install the battery cabinet refer to the Powerware 9390 Battery Cabinet Installation Manual listed in paragraph 1 4 Once battery cabinet is installed return to paragraph 3 2 3 to wire the UPS and battery cabinet 3 2 3 Installing UPS External and Battery Power Wiring NOTE The UPS cabinet is shipped with a debris shield covering the ventilation grill on top of the unit Do not remove th...

Страница 24: ...l bypass input power wiring from source to the Bypass Input Terminals and Neutral Terminals in the UPS cabinet See Appendix A for wiring and termination requirements and wiring access information Note wiring connections for dual feed systems 13 Connect phase A B and C and Neutral power wiring from Output Terminals and Neutral Terminals to the critical load See Appendix A for wiring and termination...

Страница 25: ...he UPS cabinet see Drawing 164201535 8 starting on page A 19 4 If installing interface wiring from the bottom of the cabinet proceed to Step 5 otherwise proceed to Step 7 5 Remove screws securing top internal safety shield panel and open panel to gain access to bottom entry wireway 6 Remove screws securing bottom internal safety shield panel and remove panel to gain access to bottom entry conduit ...

Страница 26: ...e UPS cabinet Refer to Appendix A and to the Powerware 9390 Battery Cabinet Installation Manual listed in paragraph 1 4 for wiring access information 7 Connect wiring to TB2 terminals 8 Proceed to Step 16 9 If installing interface wiring from the bottom of the cabinet proceed to Step 5 otherwise proceed to Step 7 10 Remove screws securing top internal safety shield panel and open panel to gain acc...

Страница 27: ...wire entry conduit landing plate to drill or punch conduit holes see Drawing 164201535 6 on page A 14 4 Reinstall conduit landing plate and install conduit 5 Route and install LAN telephone and other cables to appropriate X Slot cards 6 Close door and secure with latch 7 Refer to the manual supplied with the X Slot card for user instructions 3 2 5 Installing Accessories To install optional accesso...

Страница 28: ...n Make a copy of the Installation Checklist before filling it out and retain the original After the installation is complete a service representative will be able to verify the operation of the UPS system and commission it to support the critical load The service representative cannot perform any installation tasks other than verifying software and operating setup parameters Service personnel may ...

Страница 29: ...led All telephone and LAN connections have been completed A ground conductor is properly installed Air conditioning equipment is installed and operating correctly The area around the installed UPS system is clean and dust free It is recommended that the UPS be installed on a level floor suitable for computer or electronic equipment Adequate workspace exists around the UPS and other cabinets Adequa...

Страница 30: ...___________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ __________________...

Страница 31: ...er globes and boots 쑺 ELECTRIC ENERGY HAZARD Do not attempt to alter any battery wiring or connectors Attempting to alter wiring can cause injury 쑺 Replace batteries with the same number and type of batteries as originally installed in the UPS C A U T I O N 쑺 The installation of batteries should be performed by qualified service personnel knowledgeable of batteries and required precautions Keep un...

Страница 32: ...hin the UPS NOTE The DC input to the UPS is protected by internal fuses F30 and F31 Install batteries in accordance with the battery and battery rack manufacturer s instructions 4 3 Recycling the Used Battery Contact your local recycling or hazardous waste center for information on proper disposal of the used battery W A R N I N G 쑺 Do not dispose of the battery or batteries in a fire Batteries ma...

Страница 33: ... plate to punch conduit holes see Drawing 164201535 6 on page A 14 1 Securely mount the REPO station Recommended locations include operator s consoles or near exit doors See Drawing 164201535 10 on page A 26 for enclosure dimensions and wiring knockouts 2 Be sure the UPS system is turned off and all power sources are removed See Chapter 9 UPS Operating Instructions for shutdown instructions 3 If n...

Страница 34: ...5 8 starting on page A 19 9 Route and connect wiring as shown in Table 5 1 and Table 5 2 10 Connect jumper wire between pins 8 and 9 on TB1 if the normally closed EPO contact is not used Table 5 1 REPO Wire Terminations From REPO Station s To Customer Interface Terminal Board TB1 in UPS Cabinet Remarks TB1 4 TB 7 Twisted Wires 2 TB1 5 TB 9 Twisted Wires 2 14 18 AWG Table 5 2 REPO 7 NO 8 NC TWISTED...

Страница 35: ...allel with the first REPO 12 If required install wiring from the REPO station to trip circuitry of upstream protective devices A normally open contact is provided between terminals 6 and 7 of REPO as shown in Figure 5 1 REPO switch wiring must be in accordance with UL Class II requirements 13 When all wiring is complete reinstall safety shield panels removed in previous steps 14 Close door and sec...

Страница 36: ...Installing a Remote Emergency Power Off Control 5 4 Powerware 9390 UPS 40 80 kVA Installation and Operation Manual S 164201535 Rev A This page intentionally left blank ...

Страница 37: ...5 5 Powerware 9390 UPS 40 80 kVA Installation and Operation Manual S 164201535 Rev A Section II Operation ...

Страница 38: ...5 6 Powerware 9390 UPS 40 80 kVA Installation and Operation Manual S 164201535 Rev A This page intentionally left blank ...

Страница 39: ...kout overvoltage undervoltage and out of tolerance frequency conditions The basic system consists of a rectifier battery converter inverter monitoring operation control panel integrated communications server and microprocessor controlled DSP logic In this manual the power required by your equipment is called the critical load The UPS supplies the critical load with conditioned power that is synchr...

Страница 40: ...de the critical load is supplied by the inverter which derives its power from rectified utility AC power In this mode the battery charger also provides charging current for the battery if needed 쑺 In Battery mode the battery provides DC power which maintains inverter operation The battery supports the critical load 쑺 In Bypass mode the critical load is directly supported by utility power The UPS c...

Страница 41: ...ont panel and indicates the incoming power is within voltage and frequency acceptance windows Three phase AC input power is converted to DC utilizing IGBT devices to produce a regulated DC voltage to the inverter The battery is charged directly from the regulated rectifier output through a buck or boost DC converter depending on a 208 or 480 volt system and the size of the battery string attached ...

Страница 42: ...dth modulation PWM to produce a regulated and filtered AC output The AC output of the inverter is delivered to the system output through the output contactor K3 If the utility AC power is interrupted or is out of specification the UPS automatically switches to Battery mode to support the critical load with no interruption When utility power returns the UPS returns to Normal mode If the UPS becomes...

Страница 43: ...f the system is not protected from voltage or frequency fluctuations or power outages from the source Some power line filtering and spike protection is provided to the load but no active power conditioning or battery support is available to the output of the system in the Bypass mode of operation The internal bypass is comprised of a solid state silicon controlled rectifier SCR static switch SSW a...

Страница 44: ...itch and opening the output contactor K3 This kind of transfer is normally referred to as a Make Before Break transfer The transfer should take place in less than 4 mS quarter cycle to ensure loads on the systems output are not interrupted The static switch remains on until either the inverter is able to support the system output or the unit is placed into a maintenance position where repairs can ...

Страница 45: ...rrent required to support the inverter The input contactor K1 is opened and energy stored in the battery is supplied instantaneously to the battery converter The converter either bucks or boosts the voltage so that the inverter can support the customers load without interruption If the bypass is common with the rectifier input the Feed Back Protection contactor K5 will also open The opening of con...

Страница 46: ...tead of shuting down If at any time during the battery discharge the input power becomes available again contactors K1 and K5 are closed and the rectifier will begin to supply DC current to the converter and inverter At this point the unit returns to normal operation Depending on the amount of load on the system and the duration of the battery discharge battery current limit alarms may be seen for...

Страница 47: ...harges the energy storage elements in the power train prior to energizing the rectifier 6 3 2 Inverter The Inverter is a three phase high frequency PWM IGBT based power conversion stage that continuously supplies the critical load with high quality AC power The IGBTs are modulated to maintain the highest efficiency 6 3 3 Battery Charger The charger is also a high frequency IGBT based power convers...

Страница 48: ...Understanding UPS Operation 6 10 Powerware 9390 UPS 40 80 kVA Installation and Operation Manual S 164201535 Rev A This page intentionally left blank ...

Страница 49: ...tact One alarm contact is provided for connection to equipment at the facility such as a light an audible alarm or a computer terminal The equipment connected to these contacts alert you to a UPS alarm See Chapter 10 Using Features and Options for additional information 7 1 3 X Slot Communication Bay A two slot communication bay is standard equipment with an additional two slot bay available as an...

Страница 50: ...anced by equipping the UPS system with up to four Powerware 9390 battery cabinets containing sealed lead acid maintenance free batteries The battery cabinets are designed for line up and match installation and are available in 192 cell 208V units only 216 cell and 240 cell configurations 7 2 2 Optional X Slot Cards The optional X Slot cards support several protocols such as SNMP HTTP AS 400 and Mo...

Страница 51: ...ONTINUE Figure 8 1 UPS Control Panel The control panel consists of the following 쑺 A liquid crystal display LCD 1 쑺 A horizontal row of pushbutton switches 2 쑺 A vertical column of status indicators 3 The following paragraphs describe using the UPS control panel to monitor the UPS See Chapter 9 UPS Operating Instructions for use of the operational controls When the unit powers up the screen displa...

Страница 52: ...and notices see Chapter 11 Responding to System Events B The information area contains data about UPS status and operations Select a menu option to display the desired information C The menu bar lists the titles of the available screens To select a screen press the pushbutton underneath the desired screen D Navigation pushbuttons Function changes depending on the screen displayed Use to select men...

Страница 53: ...e stamp configure the UPS serial communication ports and view the firmware version numbers LOAD OFF De energizes the critical load and powers down the UPS Returns to Main Menu and Mimic screen from the Events Meters Controls or System Setup screens Returns to the main System Setup Level screen from a setup submenu 8 2 1 Mimic Screen Figure 8 3 shows the Main Menu and Mimic screen To select the Mim...

Страница 54: ... currently active The most recent event is listed first As events clear they are removed from the Active System Events listing Figure 8 4 shows the Active Events screen To scroll through the events press the or pushbuttons on the menu bar ACTIVE EVENTS HISTORY ALARM INPUT AC UNDERVOLTAGE ALARM BYPASS AC UNDER VOLTAGE NOTICE BATTERY VOLTAGE LOW NOTICE NO SYNC ON NOTICE BYPASS NOT AVAILABLE NOTICE C...

Страница 55: ...r and service status 쑺 User instruction 쑺 User alarm 쑺 Check UPS 쑺 Schedule service 쑺 UPS shutdown 쑺 Service alarm The end of the log the most recent events appears when you display the screen and you must scroll upward to view older event listings Figure 8 5 shows the History Log screen To scroll through the events press the or pushbuttons on the menu bar To return to the Active Events screen pre...

Страница 56: ... 8 10 show the Unit Meter screens To scroll through the meter screens press the or pushbuttons on the menu bar The current UPS readings are displayed in the information area of the screen The Output screen shows output voltage phase to neutral output current each phase and frequency being supplied by the UPS followed by the KVA KW and power factor measurements V1 V2 V3 KVA KW PF I1 I2 I3 FREQ OUTP...

Страница 57: ...oming utility source followed by the KVA KW and power factor measurements INPUT V1 V2 V3 KVA KW PF I1 I2 I3 FREQ LEAD Figure 8 7 Input Meter Screen The Bypass screen shows the bypass input voltage phase to neutral output current each phase and frequency of the incoming utility source followed by the KVA KW and power factor measurements BYPASS V1 V2 V3 KVA KW PF I1 I2 I3 FREQ LEAD Figure 8 8 Bypass...

Страница 58: ...the minutes of battery time remaining When battery life decreases to less than 20 Check Battery is displayed VDC IDC TIME REMAINING V A MINUTES BATTERY Figure 8 9 Battery Meter Screen The Output Current Screen displays a real time bar graph of the output current of the UPS The graph shows the current for each phase L2 L3 125 100 75 50 25 0 OUTPUT CURRENT L1 Figure 8 10 Output Current Load Meter Sc...

Страница 59: ...show the firmware versions installed identify the unit type and enter a password to access Level 1 functions see paragraph 8 2 5 No password is necessary to access Level 0 functions Figure 8 11 shows the System Setup Level 0 menu screen Use the or pushbuttons to highlight the setup function screen desired then press the SELECT pushbutton to display the function screen ENTER PASSWORD CONTRAST ADJUS...

Страница 60: ...st screen Figure 8 12 shows the Contrast Adjust screen Use the or pushbuttons to adjust the contrast for the LCD When the contrast adjustment is complete press the SAVE pushbutton Once the setting is saved the System Setup screen will be displayed To return to the System Setup screen without saving the setting press the pushbutton CONTRAST ADJUST 70 SAVE Figure 8 12 Contrast Adjust Screen ...

Страница 61: ...ushbuttons on the menu bar To return to the System Setup screen press the pushbutton DSP DISPLAY MINI CSB 57 00 0 54 GATE DRIVE 3 00 0 00 VERSIONS PLD 1 BOOTLOADER 0 00 Figure 8 13 Versions Screen Select UNIT TYPE from the System Setup Level 0 menu to display the Unit Type screen The Unit Type screen provides the model CTO and serial numbers of the UPS unit Figure 8 14 shows the Unit Type screen T...

Страница 62: ... PASSWORD from the System Setup Level 0 menu to display the Enter Password screen Figure 8 15 shows the Enter Password screen Use the or pushbuttons to select the password character position Use the or pushbuttons to change the password character Once the password is entered press the DONE pushbutton The System Setup Level 1 menu screen is displayed The default password is L1 L1 ENTER PASSWORD DON...

Страница 63: ... available Figure 8 16 shows the System Setup Level 1 screen Use the or pushbuttons to highlight the setup function screen desired then press the SELECT pushbutton to display the function screen The Level 1 screen will timeout after 60 minutes or can be logged out at any time by selecting the LOG OUT function from the menu screen ENTER PASSWORD LOG OUT CONTRAST ADJUST VERSIONS CHANGE PASSWORD ENTE...

Страница 64: ...nge Password screen allows the System Setup Level 1 password to be changed Figure 8 17 shows the Change Password screen Use the or pushbuttons to select the password character position Use the or pushbuttons to change the password character Once the new password is entered press the DONE pushbutton The Change Password Save screen is displayed NEW OLD L1 L1 CHANGE PASSWORD DONE Figure 8 17 Change P...

Страница 65: ... be saved aborted or to retry another password Figure 8 18 shows the Change Password Save screen Press SAVE RETRY or ABORT If SAVE or ABORT is pressed the action is completed and the System Setup screen will be displayed If RETRY is pressed the Change Password screen is redisplayed NEW OLD L1 L1 CHANGE PASSWORD ABORT SAVE RETRY Figure 8 18 Change Password Save Screen ...

Страница 66: ...ction of the either month date year or date month year formats for display on the screen and used for logging events in the Event and History Logs Figure 8 19 shows the Time Format screen Use the or pushbuttons to highlight the desired format then press the SELECT pushbutton to display the Set Date and Time screen To return to the System Setup screen press the pushbutton MM DD YYYY DD MM YYYY TIME...

Страница 67: ...s in the Event and History Logs Figure 8 19 shows the Date and Time MM DD YYYY screen Use the or pushbuttons to highlight the setting to be changed Use the or pushbuttons to make the change When finished making changes use the or pushbuttons to highlight SAVE and the or pushbuttons to select YES To complete the save function and return to the System Setup screen select the pushbutton DATE MONTH YE...

Страница 68: ...s in the Event and History Logs Figure 8 19 shows the Date and Time DD MM YYYY screen Use the or pushbuttons to highlight the setting to be changed Use the or pushbuttons to make the change When finished making changes use the or pushbuttons to highlight SAVE and the or pushbuttons to select YES To complete the save function and return to the System Setup screen select the pushbutton DATE MONTH YE...

Страница 69: ...lay the Serial Port Setup screen This screen allows selection of the serial COM port to set up Figure 8 22 shows the Serial Port Setup screen Use the or pushbuttons to highlight the the COM port to be set up then press the SELECT pushbutton To return to the System Setup screen press the pushbutton COM PORT SETUP COM 1 COM 3 COM 2 SELECT Figure 8 22 Serial Port Setup Screen ...

Страница 70: ...ayed If the changes are not wanted the ABORT pushbutton may be used to return to the Serial Port Setup screen Figure 8 22 shows the COM Setup screen Use the or pushbuttons to highlight the setting to be changed Use the pushbutton to toggle through the values for the setting to make the change Press SAVE or ABORT Once the action is completed the Serial Port Setup screen appears BAUD RATE PARITY DAT...

Страница 71: ...s are controlled from this screen In addition the screen displays the current status of the UPS and indicates whether the UPS is in Maintenance Bypass or Bypass and the state of the Power Module PM and battery charger Figure 8 24 and Figure 8 25 show the System Controls screens Use the or pushbuttons on the menu bar to toggle the menu bar functions between System Controls Screens 1 and 2 MAINTENAN...

Страница 72: ...CE BYPASS BYPASS POWER MODULE PM OFF OFF ONLINE CHARGER OFF Figure 8 25 System Controls Screen 2 The CHGR pushbutton switch on the System Controls screen toggles the charger function On and Off The PM pushbutton switch toggles the Power Module function On and Off For detailed information about using the System Controls see Chapter 9 UPS Operating Instructions ...

Страница 73: ...from the Main Menu bar or System Controls Menu bar This screen allows the LOAD OFF process to be aborted if the LOAD OFF pushbutton was pressed accidentally Figure 8 26 shows the Load Off screen For detailed information about using the LOAD OFF and Shutdown screen see Chapter 9 UPS Operating Instructions HOLD LOAD OFF BUTTON FOR 3 SECONDS TO TURN OFF LOAD LOAD OFF CANCEL Figure 8 26 Load Off Scree...

Страница 74: ...ated The indicator continues to flash until acknowledged by pressing any control panel pushbutton once Battery This yellow indicator is illuminated when the UPS is operating in Battery mode Because Battery mode is a normal condition of the UPS the Normal indicator also remains illuminated Bypass This yellow indicator is illuminated when the UPS is operating in Bypass mode The critical load is supp...

Страница 75: ...ay becoming active indicating logic power 4 Press the CONTROLS pushbutton on the Main menu bar The System Controls screen appears 5 On the System Controls screen the Power Module PM status should indicate SHUTDOWN 6 Press the NORMAL pushbutton on the System Controls menu bar If Auto Bypass is enabled the critical load is immediately supplied by the bypass source in Bypass mode until the inverter t...

Страница 76: ...ars 5 On the System Controls screen the Power Module PM status should indicate SHUTDOWN 6 Press the BYPASS pushbutton on the System Controls menu bar The critical load is immediately supplied by the bypass source in Bypass mode 7 The UPS is now operating in the bypass mode and the BYPASS status indicator is illuminated 9 3 Starting the Power Module To start the Power Module without transferring th...

Страница 77: ...rocedure C A U T I O N In Bypass Mode the critical load is not protected from commercial power interruptions and abnormalities 1 Press the CONTROLS pushbutton on the Main menu bar The System Control screen appears 2 Press the BYPASS pushbutton on the System Controls menu bar The UPS switches to Bypass mode and the critical load is immediately supplied by the bypass source If the bypass source is n...

Страница 78: ...ating in the Normal mode and the NORMAL status indicator illuminates The Power Module PM status indicates ONLINE 9 6 Transfer from Normal to Bypass Mode with UPS Shutdown 1 Transfer the critical load to bypass by performing procedure in paragraph 9 4 2 Press the CONTROLS pushbutton on the Main menu bar The System Control screen appears 3 Press the pushbutton to display System Controls Screen 2 4 P...

Страница 79: ...contactors open the battery breaker or disconnect is tripped and the Power Module is turned off W A R N I N G Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened 3 Open the UPS input and bypass if dual feed feeder circuit breakers 9 8 Charger Control To turn the battery charger on or off perform the following procedure 1 Press the CONTROLS pushbutton o...

Страница 80: ... proceed or abort the shutdown C A U T I O N All power to the critical load is lost when the LOAD OFF is selected in the following step You should use this feature only when you want to de energize the critical load 2 To shut down the UPS press LOAD OFF from the Load Off Menu bar and hold for three seconds To abort the shutdown press CANCEL When LOAD OFF is selected and held for three seconds the ...

Страница 81: ...ted in the following step You should use this feature only when you want to de energize the critical load NOTE The following instructions are for the Powerware supplied REPO switch If a customer supplied REPO switch is used it may not activate in the same manner refer to the operating instructions provided with the switch 1 Press the REPO pushbutton switch The input output and bypass backfeed cont...

Страница 82: ...UPS Operating Instructions 9 8 Powerware 9390 UPS 40 80 kVA Installation and Operation Manual S 164201535 Rev A This page intentionally left blank ...

Страница 83: ...e customer interface terminals for external connections are located inside the UPS Regardless of how you assign the building alarms they display as Building Alarm 1 and Building Alarm 2 on the control panel You should use twisted pair wires for each alarm input and common 10 2 General Purpose Relay Contact One general purpose relay contact is provided as a standard feature on the UPS The alarm con...

Страница 84: ...Using Features and Options 10 2 Powerware 9390 UPS 40 80 kVA Installation and Operation Manual S 164201535 Rev A This page intentionally left blank ...

Страница 85: ... event needing attention is taking place Horn 1 cycles on for 1 second at a one second rate 11 3 System Event Indicators The status indicators on the UPS control panel work in conjunction with the event horn to let you know when the UPS system is operating in any mode other than Normal Only the Normal indicator is visible during normal UPS system operation The others light to indicate alarms or ev...

Страница 86: ...witchgear OK Off No 1 HA Condition Cleared Check Inv Temperature Sensor 1 No 1 HA Service Required Check Inv Temperature Sensor OK Off No 1 HA Condition Cleared Check Inverter 1 1 1 HA Service Required Check Logic Power Supply 1 No 1 HA Service Required Check Logic Power Supply OK Off No 1 HA Condition Cleared Check Output Switchgear 1 No 1 HA Service Required Check Output Switchgear OK Off No 1 H...

Страница 87: ... No 1 HA Condition Cleared L1 Overload 1 No 1 HA User Action Required L1 Overload OK Off No 1 HA Condition Cleared L1 Overload Extreme Level 1 No 1 HA User Action Required L1 Overload Extreme Level OK Off No 1 HA Condition Cleared L1 Overload High Level 1 No 1 HA User Action Required L1 Overload High Level OK Off No 1 HA Condition Cleared L2 Overload 1 No 1 HA User Action Required L2 Overload OK O...

Страница 88: ...rip OK Off No 1 HA Condition Cleared Rectifier Overtemperature 1 No 1 HA Service Required Rectifier Overtemperature OK Off No 1 HA Condition Cleared Remote Emergency Power Off 1 No 1 HA User Action Required Remote Emergency Power Off OK Off No 1 HA Condition Cleared Shutdown Imminent 1 No 1 HA User Action Required Shutdown Imminent OK Off No 1 HA Condition Cleared Software Incompatibility 1 No 1 H...

Страница 89: ...No No A Condition Cleared Bypass Source Out of Tolerance 1 No No HA Investigate UPS Bypass Source Out of Tolerance OK Off No No HA Condition Cleared Bypass Under or Over Frequency 1 No No HA Information Only Bypass Under or Over Frequency OK Off No No HA Condition Cleared Charger Off Command 1 No No HA Information Only Charger On Command 1 No No HA Information Only Charger Over Voltage or Current ...

Страница 90: ...o A Information Only Inverter On Command 1 No No HA Information Only Inverter Output Overcurrent 1 No No HA Information Only Inverter Phase Rotation 1 No No HA Information Only Inverter Phase Rotation OK Off No No HA Condition Cleared Load Dumped Load Power Off 1 1 No HA Investigate UPS Load Dumped Load Power Off OK Off No No HA Condition Cleared Load Off Command Executed 1 No No HA Information On...

Страница 91: ... Only Rectifier Input Over Current 1 No No A Information Only UPS Module Off 1 No No A Information Only UPS Module Off OK Off No No A Condition Cleared UPS on Battery 1 No No A Investigate UPS UPS on Battery OK Off No No A Condition Cleared UPS on Bypass 1 No No A Investigate UPS UPS on Bypass OK Off No No A Condition Cleared UPS on Generator 1 No No A Information Only UPS on Generator OK Off No N...

Страница 92: ...Started No No No H User Status Inverter Status Off No No No No User Status Inverter Status On No No No No User Status Modem Call Completed Successfully No No No H User Status Modem Connection Established No No No H User Status Outgoing Modem Call Started No No No H User Status Output Switchgear Open No No No H User Status Output Switchgear Open OK No No No H User Status Rectifier Phase L1 Current ...

Страница 93: ... COMMAND Message Horn Phone Relay Log Indication Load Off Command Received Yes No No H Information Only To Normal Mode Command No No No H Information Only To Bypass Command No No No H Information Only Log codes indicate where the UPS records the event H History log HA History and Active logs and A Active log only ...

Страница 94: ...Responding to System Events 11 10 Powerware 9390 UPS 40 80 kVA Installation and Operation Manual S 164201535 Rev A This page intentionally left blank ...

Страница 95: ...ilt in switching hub that allows three additional network devices to be connected to the network without the requirement of additional network drops 쑺 Modem Card provides out of band remote notification and monitoring using modem communication directly to cell phones and pagers 쑺 Relay Interface Card AS 400 has isolated dry contact Form C relay outputs for UPS status Utility failure Low battery UP...

Страница 96: ...their specific needs 12 3 Remote Notification For connection and set up of a modem or to enable Remote Notify and Call Home features within the UPS please contact Powerware see page 1 4 Remote Notification provides the UPS with the capability to use a standard off the shelf PC modem as a telephone interface The features provided by this option are as follows 쑺 Call out to a remote terminal or page...

Страница 97: ...ng function maintains the link between the UPS and modem 12 4 Terminal Mode In Terminal Mode the user can request the following NOTE The brackets in the following bullets indicate standard keyboard characters To use a key combination hold down the Escape key and press the indicated letter key 쑺 Display UPS control panel by pressing and holding ESC then press V 쑺 Display Event History by pressing a...

Страница 98: ...ntinually logged through the serial port to the device connected to the port The printed log entries contain a time and date stamp and the alarm text message Terminal mode uses this format for printing alarm entries MM DD YYYY HH MM SS hh KYWD MESSAGE CR LF Where Equals MM Month 2 digits YYYY Year 4 digits DD Day 2 digits HH Hour 2 digits MM Minute 2 digits SS Second 2 digits hh Hundredths of Seco...

Страница 99: ... Under Voltage 03 11 2004 14 27 16 464 ALARM Battery Under Voltage 03 11 2004 14 27 18 954 NOTICE Battery Voltage Low 03 11 2004 14 27 19 169 NOTICE Battery Not Present 03 11 2004 14 27 40 714 STATUS PPU Shutdown 03 11 2004 14 28 04 023 NOTICE Check Modem 03 12 2004 14 15 09 000 STATUS CSB Power Supply On 03 12 2004 14 15 09 043 NOTICE Inverter Initializing 03 12 2004 14 15 11 725 STATUS UPS Power...

Страница 100: ...Communication 12 6 Powerware 9390 UPS 40 80 kVA Installation and Operation Manual S 164201535 Rev A This page intentionally left blank ...

Страница 101: ...e attempting internal access to the UPS module W A R N I N G 쑺 Servicing and maintenance should be performed by qualified service personnel only 쑺 LETHAL VOLTAGE PRESENT This unit should not be operated with the cabinet doors open or protective panels removed Do not make any assumptions about the electrical state of any cabinet in the UPS system Since each battery string is an energy source in its...

Страница 102: ...es Released electrolyte is harmful to the skin and eyes and may be toxic 쑺 A battery can cause electrical shock burn from high short circuit current or fire Observe proper precautions A T T E N T I O N 쑺 Une batterie peut prêsenter un risque de choc êlectrique de brulure ou d incendie Suivre les précautions qui s imposent 쑺 Pour le remplacement utiliser le même nombre et modéle des batteries 쑺 L é...

Страница 103: ...lide new filter into brackets until seated on bottom brackets d Close door and secure with latch 3 Record the check results and any corrective actions in a suitable log 13 2 3 ANNUAL Maintenance Annual preventive maintenance should be performed only by authorized service personnel familiar with maintenance and servicing of the UPS system Contact your Powerware service representative for more infor...

Страница 104: ...Maintaining the UPS System 13 4 Powerware 9390 UPS 40 80 kVA Installation and Operation Manual S 164201535 Rev A This page intentionally left blank ...

Страница 105: ...0 kVA 50 60 Hz The following sections detail the input output environmental and battery specifications for the UPS 14 2 UPS System Input Operating Input Voltage Nominal 10 15 208 Vac for operation from 177 Vac to 229 Vac 480 Vac for operation from 408 Vac to 528 Vac Operating Input Frequency Range 5 Hz Operating Input Current See Appendix A Table E or Table F Reduced for Generator Adjustable Input...

Страница 106: ...ning Synchronous to Bypass Bypass within voltage limits of 5 8 of output setting bypass within 0 5 Hz Frequency Slew Rate 1 Hz per second maximum Overload Capability 110 for 10 minutes 125 for 30 seconds 150 for 10 seconds 14 4 Environmental Specifications Operating Temperature 0 to 40 C 32 104 F without derating The recommended operating temperature is 25 C 77 F Operating Altitude Maximum 1500m 5...

Страница 107: ...Battery Type Sealed maintenance free high rate discharge lead acid cells Nominal Battery String Voltage 384 Vdc 192 cells 2V cell 208V units only 432 Vdc 216 cells 2V cell 480 Vdc 240 cells 2V cell Float Charging 2 25 Vdc per cell 432 Vdc based on 192 cells 486 Vdc based on 216 cells 540 Vdc based on 240 cells Equalizing Charge 2 40 Vdc per cell set to 2 25 Vdc at factory Battery Charge Current Li...

Страница 108: ...Product Specifications 14 4 Powerware 9390 UPS 40 80 kVA Installation and Operation Manual S 164201535 Rev A This page intentionally left blank ...

Страница 109: ...01535 1 Typical Powerware 9390 UPS System 쑺 164201535 2 Physical Features and Requirements 쑺 164201535 3 UPS System Oneline Configurations 쑺 164201535 4 UPS System Oneline Drawing 쑺 164201535 5 Power Wiring Installation Notes 쑺 164201535 6 Conduit and Wire Entry Locations 쑺 164201535 7 UPS Power Terminal Locations 쑺 164201535 8 Interface Wiring Installation Notes and Terminal Locations 쑺 164201535...

Страница 110: ...WING NO SHEET REVISION 164201535 1 1 of 1 TYPICAL POWERWARE 9390 UPS SYSTEM 062504 A BATTERY CABINET UPS CABINET Installation Information A 2 Powerware 9390 UPS 40 80 kVA Installation and Operation Manual S 164201535 Rev A ...

Страница 111: ...Weight Component Model Weight Kg lb Component Model Shipping Installed Point Loading UPS Cabinet 9390 80 40 kVA 208V 208V 313 690 290 640 4 at 72 5 160 UPS Cabinet 9390 80 40 kVA 480V 480V 271 618 258 568 4 at 64 5 142 UPS Cabinet 9390 80 80 kVA 208V 208V 313 690 290 640 4 at 72 5 160 UPS Cabinet 9390 80 80 kVA 480V 480V 271 618 258 568 4 at 64 5 142 5 The clearances required around the UPS cabine...

Страница 112: ...perature Range 0 40 C 32 104 F Recommended Operating Range 20 25 C 68 77 F Maximum Relative Humidity 95 noncondensing The UPS ventilation requirements are shown in Table C Table C Air Conditioning or Ventilation Requirements During Full Load Operation Ratings Input Output Voltage Heat Rejection BTU hr 1000 hr Kg cal hr 40 kVA 208 208 11 8 2 98 40 kVA 480 480 10 9 2 76 80 kVA 208 208 27 2 6 86 80 k...

Страница 113: ...A 5 Powerware 9390 UPS 40 80 kVA Installation and Operation Manual S 164201535 Rev A Table D UPS System Oneline Configurations Oneline Drawing 164201535 4 UPS Model Vin Vout System Type Sheet 1 9390 80 40 208 208 Single Module Reverse Transfer Sheet 1 9390 80 40 9390 80 80 480 480 Single Module Reverse Transfer Single or Dual Feed ...

Страница 114: ... 8 Powerware 9390 40 80 kVA UPS SYSTEM 208V INPUT AND 208V OUTPUT 480V INPUT AND 480 V OUTPUT SINGLE OR DUAL FEED INPUT CONTACTOR K1 BATTERY CONVERTER BATTERY CABINET BATTERY BREAKER X SLOT INTERFACE Optional DUAL FEED AC INPUT TO UPS RECTIFIER AND BYPASS DUAL FEED SINGLE FEED FUSE E1 E2 E3 E6 E7 E8 E12 BACKFEED CONTACTOR K5 OUTPUT CONTACTOR K3 E4 E5 E9 E10 E11 E12 FUSE 4 WIRE A B C ROTATION ALARM...

Страница 115: ...Load Full Load Current 3 1 Neutral 1 gnd Amps 111 48 AC OUTPUT Full Load Current 3 1 Neutral 1 gnd Minimum conductor size number per AWG or kcmil ea 2 0 1 4 1 Read and understand the following notes while planning and performing the installation 1 Refer to national and local electrical codes for acceptable external wiring practices 2 Material and labor for external wiring requirements are to be pr...

Страница 116: ...S Rectifier 0 98min PF 3 1 Neutral 1 gnd Amps 240 105 AC INPUT 3 1 Neutral 1 gnd Minimum conductor size number per AWG or kcmil ea 2 0 2 1 0 1 Includes full load current plus battery recharge current AC AC Input to UPS Bypass Full Load Current 3 1 Neutral 1 gnd Amps 222 96 AC INPUT Full Load Current 3 1 Neutral 1 gnd Minimum conductor size number per AWG or kcmil ea 2 0 2 1 0 1 DC INPUT DC Input f...

Страница 117: ...in Hex E8 Phase C 1 6 350 kcmil 42 4 375 3 8 in Hex AC Input to UPS Rectifier C E1 Phase A 1 6 350 kcmil 42 4 375 3 8 in Hex p CB1 Dual Input E2 Phase B 1 6 350 kcmil 42 4 375 3 8 in Hex Dual Input E3 Phase C 1 6 350 kcmil 42 4 375 3 8 in Hex AC Input To Bypass Dual E6 Phase A 1 6 350 kcmil 42 4 375 3 8 in Hex p yp Input E7 Phase B 1 6 350 kcmil 42 4 375 3 8 in Hex E8 Phase C 1 6 350 kcmil 42 4 37...

Страница 118: ...1 Phase A 1 14 2 0 13 5 120 3 16 in Hex p Dual Input E2 Phase B 1 14 2 0 13 5 120 3 16 in Hex E3 Phase C 1 14 2 0 13 5 120 3 16 in Hex AC Input To Bypass Dual E6 Phase A 1 14 2 0 13 5 120 3 16 in Hex p yp Input E7 Phase B 1 14 2 0 13 5 120 3 16 in Hex E8 Phase C 1 14 2 0 13 5 120 3 16 in Hex Single Feed Jumper from Phase A N A 5 6 50 1 4 20 Hex Nut g p Rectifier Input Terminals to Bypass Input Ter...

Страница 119: ... size neutral 11 Conduit sizes were chosen from NEC Table C1 type letters RHH RHW RHW 2 TW THW THHW THW 2 Table I Power Cable Conduit Requirements UPS Model Voltage Terminal Number of Wires in Conduit Minimum Conduit Trade Size inches Number of Conduits AC Input to UPS A B C Gnd 4 2 1 2 1 9390 80 40 208 AC AC Input to Bypass A B C Neut Gnd 5 2 1 2 1 9390 80 40 C Output A B C Neut Gnd 5 2 1 2 1 DC ...

Страница 120: ...ed 300A 125A CAUTION To reduce the risk of fire connect only to a circuit provided with maximum input circuit breaker current ratings from Table J in accordance with the National Electrical code ANSI NFPA 70 14 Source protection for the AC input should be treated as if you were supplying a 40 kVA or 80 kVA three phase transformer to allow for inrush current 15 The line to line unbalanced output ca...

Страница 121: ...ts the maximum rating for continuous duty rated circuit breakers satisfying the criteria for both Table L Maximum DC Input Circuit Breaker Ratings UPS Model Input Voltage Rating UPS Model 208V 480V 9390 80 40 150A 150A 9390 80 80 300A 300A 20 Battery voltage is computed at 2 volts per cell as defined by Article 480 of the NEC Rated battery current is computed at 2 volts per cell 21 The battery wir...

Страница 122: ...DC INPUT DC CONTROL AND INTERFACE CONNECTIONS REMOVE PANEL TO DRILL OR PUNCH CONDUIT HOLES BOTTOM ENTRY CONDUIT LANDING FOR AC INPUT AND OUTPUT DC INPUT DC CONTROL AND INTERFACE CONNECTIONS REMOVE PANEL TO DRILL OR PUNCH CONDUIT HOLES CONDUIT LANDINGS FOR X SLOT CONNECTIONS REMOVE PANELS TO DRILL OR PUNCH CONDUIT HOLES TOP VIEW BOTTOM VIEW Installation Information A 14 Powerware 9390 UPS 40 80 kVA...

Страница 123: ... UPS RECTIFIER AND BYPASS A B C N DC INPUT FROM BATTERY TO UPS AND AC OUTPUT TO CRITICAL LOAD A B C N WIREWAY FOR TOP ENTRY POWER WIRING BATTERY WIRING ACCESS KNOCKOUT REMOVE KNOCKOUT TO ROUTE WIRES FROM INTEGRAL BATTERY CABINET SEE SHEET 2 FOR DETAILS BATTERY WIRING ACCESS KNOCKOUT REMOVE KNOCKOUT TO ROUTE WIRES FROM INTEGRAL BATTERY CABINET Installation Information A 15 Powerware 9390 UPS 40 80 ...

Страница 124: ... TO UPS RECTIFIER DUAL INPUT AC INPUT TO UPS RECTIFIER AND BYPASS SINGLE INPUT AC INPUT TO BYPASS DUAL INPUT PHASE A E1 PHASE B E2 PHASE C E3 PHASE A E9 PHASE B E10 PHASE C E11 AC OUTPUT TO CRITICAL LOAD NEUTRAL TERMINALS E12 PHASE A E6 PHASE B E7 PHASE C E8 NOTE Metal shields covering wiring terminals must be removed or opened to gain access to terminals Installation Information A 16 Powerware 93...

Страница 125: ...C N SEE SHEET 4 FOR DETAILS WIREWAY FOR TOP ENTRY POWER WIRING NOTE Metal shields covering wiring terminals must be removed or opened to gain access to terminals BATTERY WIRING ACCESS KNOCKOUT REMOVE KNOCKOUT TO ROUTE WIRES FROM INTEGRAL BATTERY CABINET BATTERY WIRING ACCESS KNOCKOUT REMOVE KNOCKOUT TO ROUTE WIRES FROM INTEGRAL BATTERY CABINET Installation Information A 17 Powerware 9390 UPS 40 80...

Страница 126: ... INPUT PHASE A E1 PHASE B E2 PHASE C E3 PHASE A E9 PHASE B E10 PHASE C E11 AC OUTPUT TO CRITICAL LOAD PHASE A E1 PHASE B E2 PHASE C E3 AC INPUT TO UPS RECTIFIER AND BYPASS SINGLE INPUT AC INPUT TO BYPASS DUAL INPUT NEUTRAL TERMINALS E12 DC INPUT FROM BATTERY E4 E5 Installation Information A 18 Powerware 9390 UPS 40 80 kVA Installation and Operation Manual S 164201535 Rev A ...

Страница 127: ...ot connectivity cards must be provided by facility planners or customer Table M TB1 and TB2 Interface Connections Terminal TB1 Name Description 1 Building Alarm 1 Programmable UPS alarm Activated by a remote 2 Building Alarm 2 Programmable UPS alarm Activated by a remote dry contact closure 3 Building Alarm Return dry contact closure 4 Alarm Relay NC General purpose normally open and normally clos...

Страница 128: ...OCATIONS TB1 TB2 X SLOTS STANDARD X SLOT COMMUNICATION BAY 1 2 3 4 OPTIONAL X SLOT COMMUNICATION BAY WIREWAY FOR BOTTOM ENTRY INTERFACE WIRING NOTE Metal shields covering wiring terminals must be removed or opened to gain access to terminals Installation Information A 20 Powerware 9390 UPS 40 80 kVA Installation and Operation Manual S 164201535 Rev A ...

Страница 129: ...ignment alarms display as Building Alarm 1 and Building Alarm 2 on the Control Panel Display Screen Use twisted pair wires for each alarm input and common NOTES 1 All building alarm inputs or remote features require an isolated normally open contact or switch rated at 24 Vdc 20 mA minimum connected between the alarm input and common terminal as shown All control wiring and relay and switch contact...

Страница 130: ...rom the UPS must be connected to the DC source disconnect device 8 Battery Aux and UVR wiring should be a minimum of 18 AWG Table N Battery Disconnect Interface BATTERY BREAKER OR DISCONNECT 4 5 6 TB2 BATTERY AUX 3 BATTERY AUX BATTERY UVR BATTERY UVR UPS UV Table O Alarm Relay Contact 4 5 6 ALARM RELAY TB1 CONTACT RATING Maximum Switched Voltage 120 Vac Maximum Carrying Current 5A NOTE Relays are ...

Страница 131: ...ors in the UPS cabinet and isolates power from your critical load Local electrical codes may also require tripping upstream protective devices to the UPS 10 A jumper wire must be connected between pins 8 and 9 on TB1 if the normally closed EPO contact is not used Table P Remote EPO 7 NO 8 NC TWISTED WIRES UPS TB1 REMOTE EPO SWITCH NC REMOTE EPO SWITCH NO 9 RTN Remote EPO switch rating is 24 Vdc 1A...

Страница 132: ...NET DIMENSIONS 062504 A 164201535 9 DESCRIPTION DATE DRAWING NO SHEET REVISION FRONT VIEW RIGHT SIDE VIEW Installation Information A 24 Powerware 9390 UPS 40 80 kVA Installation and Operation Manual S 164201535 Rev A ...

Страница 133: ...EET REVISION TOP VIEW BOTTOM VIEW REMOVE DEBRIS SHIELD COVERING EXHAUST GRILL BEFORE OPERATING SYSTEM SHIELD NOT SHOWN FOR CLARITY Dimensions are in millimeters and inches Installation Information A 25 Powerware 9390 UPS 40 80 kVA Installation and Operation Manual S 164201535 Rev A ...

Страница 134: ... TO OTHER EQUIPMENT Dimensions are in millimeters and inches 2 Maximum distance between the Remote EPO and the UPS not to exceed 500 feet NOTES 1 Conduit and wiring between the Remote Emergency Power Off REPO and the UPS to be supplied by customer 3 Maximum wire size 14 AWG Minimum wire size 18 AWG Installation Information A 26 Powerware 9390 UPS 40 80 kVA Installation and Operation Manual S 16420...

Страница 135: ...ed to a new location by someone other than an authorized Powerware Customer Service Engineer in USA or Agent outside of USA or c if the Product s serial numbers have been removed or are illegible Any Warranted Items repaired or replaced pursuant to this Warranty will be warranted for the remaining portion of the original Warranty subject to all the terms thereof Labor warranty is not provided for ...

Страница 136: ...Warranty W 2 Powerware 9390 UPS 40 80 kVA Installation and Operation Manual S 164201535 Rev A This page intentionally left blank ...

Страница 137: ......

Страница 138: ... 164201535A 164201535 A ...

Отзывы: