5 of 7
POWER WIRING INSTALLATION NOTES
062504
DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
A
164201535---5
Installation Information
A-11
Powerware
®
9390 UPS (40–80 kVA) Installation and Operation Manual
S
164201535 Rev A
9.
Per NEC article 300-20(a), all three phase conductors must be run in the same conduit.
Neutral and ground must be run in the same conduit as the phase conductors.
10.
Conduit is sized to accommodate one neutral conductor the same size as the phase
conductor and one #8 AWG ground conductor. If two neutral conductors or an oversized
neutral conductor are to be installed, check the size of the conduit needed to
accommodate the extra wire or size and use that conduit size in place of the conduit size
listed in Table I. All Powerware 9390 products can accommodate a double size neutral.
11.
Conduit sizes were chosen from NEC Table C1, type letters RHH, RHW, RHW-2, TW, THW,
THHW, THW-2.
Table I. Power Cable Conduit Requirements
UPS Model
Voltage
Terminal
Number of
Wires in
Conduit
Minimum Conduit
Trade Size (inches)
Number of
Conduits
AC Input to UPS
(A, B, C, Gnd)
4
2-1/2
1
9390 80/40
208
AC
AC Input to Bypass
(A, B, C, Neut, Gnd)
5
2-1/2
1
9390---80/40
C
Output
(A, B, C, Neut, Gnd)
5
2-1/2
1
DC
Battery
(Positive), (Negative), Gnd
3
1
1
AC Input to UPS
(A, B, C, Gnd)
4
1-1/4
1
9390 80/40
480
AC
AC Input to Bypass
(A, B, C, Neut, Gnd)
5
1-1/4
1
9390---80/40
C
Output
(A, B, C, Neut, Gnd)
5
1-1/4
1
DC
Battery
(Positive), (Negative), Gnd
3
1
1
AC Input to UPS
(A, B, C, Gnd)
4
2-1/2
2
9390 80/80
208
AC
AC Input to Bypass
(A, B, C, Neut, Gnd)
5
2-1/2
2
9390---80/80
AC
Output
(A, B, C, Neut, Gnd)
5
2-1/2
2
DC
Battery
(Positive), (Negative), Gnd
3
2
1
AC Input to UPS
(A, B, C, Gnd)
4
2-1/2
1
9390 80/80
480
AC
AC Input to Bypass
(A, B, C, Neut, Gnd)
5
2-1/2
1
9390---80/80
C
Output
(A, B, C, Neut, Gnd)
5
2-1/2
1
DC
Battery
(Positive), (Negative), Gnd
3
2
1
Содержание 9390
Страница 1: ...9390 INSTALLATION OPERATION MANUAL UPS 40 80 kVA www powerware com ...
Страница 13: ...1 1 Powerware 9390 UPS 40 80 kVA Installation and Operation Manual S 164201535 Rev A Section I Installation ...
Страница 37: ...5 5 Powerware 9390 UPS 40 80 kVA Installation and Operation Manual S 164201535 Rev A Section II Operation ...
Страница 137: ......
Страница 138: ... 164201535A 164201535 A ...