Product Specifications
14-3
Powerware
®
9390 UPS (40–80 kVA) Installation and Operation Manual
S
164201535 Rev A
14.5 Battery Specifications
These specifications are for batteries supplied by the UPS manufacturer in
line-up-and-match cabinets.
Battery Type
Sealed, maintenance-free, high rate discharge, lead-acid cells
Nominal Battery String
Voltage
384 Vdc (192 cells @2V/cell) (208V units only)
432 Vdc (216 cells @2V/cell)
480 Vdc (240 cells @2V/cell)
Float Charging
2.25 Vdc per cell
(432 Vdc based on 192 cells)
(486 Vdc based on 216 cells)
(540 Vdc based on 240 cells)
Equalizing Charge
2.40 Vdc per cell, set to 2.25 Vdc at factory
Battery Charge Current
Limit
15% of rectifier capacity at full load