DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
INTERFACE WIRING INSTALLATION
NOTES AND TERMINAL LOCATIONS
Installation Information
A-22
Powerware
®
9390 UPS (40–80 kVA) Installation and Operation Manual
S
164201535 Rev A
7.
The UPS DC UVR trip and Battery Aux signal from the UPS must be connected to the DC
source disconnect device.
8.
Battery Aux and UVR wiring should be a minimum of 18 AWG.
Table N. Battery Disconnect Interface
BATTERY
BREAKER OR
DISCONNECT
4
5
6
TB2
BATTERY AUX +
3
BATTERY AUX ---
BATTERY UVR +
BATTERY UVR ---
UPS
UV
Table O. Alarm Relay Contact
4
5
6
ALARM RELAY
TB1
CONTACT RATING:
Maximum Switched Voltage:
120 Vac
Maximum Carrying Current: 5A
NOTE: Relays are shown in de-energized state. Relays change state
when the UPS is in normal operating mode.