UPS INSTALLATION PLAN AND UNPACKING
Power Xpert
9395 UPS (450–550 kVA) Installation and Operation Manual
164201701 Rev 3
www.eaton.com/powerquality
3-3
The UPS ventilation requirements are shown in Table 3‐3.
Table 3‐3. Air Conditioning or Ventilation Requirements During Full Load Operation
Rating
Input/Output
Voltage
Heat Rejection
BTU/hr
1000/ (kg-cal/hr)
Ventilation Required for
Cooling Air Exhaust
450 kVA
400/400
87 (21886)
Approximately 1652 liter/sec (3500 CFM)
With Field Installed UPM
Approximately 2478 liter/sec (5250 CFM)
480/480
88 (22107)
500 kVA
400/400
96 (24318)
480/480
97 (24563)
550 kVA
400/400
106 (26479)
480/480
107 (27020)
Dimensions are in millimeters [inches].
Figure 3‐1. UPS Cabinet Dimensions (Front View)