UPS INSTALLATION PLAN AND UNPACKING
Power Xpert
9395 UPS (450–550 kVA) Installation and Operation Manual
164201701 Rev 3
www.eaton.com/powerquality
3-15
External overcurrent protection and disconnect are not provided by this product, but
are required by codes. Refer to Table 3‐4 on page 3-9, Table 3‐5 on page 3-10, or
Table 3‐6 on page 3-11 for wiring requirements. If an output lockable disconnect is
required, it is to be supplied by the customer.
Table 3‐13 lists the recommended rating for input circuit breakers.
Table 3‐14 lists the recommended rating for input circuit breakers used with separate
rectifier inputs. A separate breaker is required for each UPM.
Table 3‐13. Recommended Input Circuit Breaker Ratings
UPS Model
Input Rating
Load Rating
400V
480V
9395-550/450
80% Rated
1000A
800A
100% Rated
800A
700A
Power Xpert 9395-550/500
80% Rated
1200A
1000A
100% Rated
1000A
700A
Power Xpert 9395-550/550
80% Rated
1200A
1000A
100% Rated
1000A
800A
Table 3‐14. Separate Rectifier Input Recommended Input Circuit Breaker Ratings
UPS Model
Input Rating for Each UPM
Load Rating
480V
480V
9395-550/450
Power Xpert 9395-550/500
Power Xpert 9395-550/550
80% Rated
500A
500A
100% Rated
400A
400A
C
A
U
T
I
O
N
To reduce the risk of fire, connect only to a circuit provided with maximum input circuit breaker current
ratings from Table 3‐13 in accordance with the NEC, ANSI/NFPA 70.
The line‐to‐line unbalanced output capability of the UPS is limited only by the full load
per phase current values for AC output to critical load shown in Table 3‐4 on
page 3-9 or Table 3‐5 on page 3-10. The recommended line‐to‐line load unbalance is
50% or less.
Bypass and output overcurrent protection and bypass and output disconnect switches
are to be provided by the customer. Module Output Breakers (MOBs) are to be
provided by the customer. Table 3‐15 lists the recommended rating for bypass,
output, and MOB circuit breakers. Bypass breakers are not required for IOM
configurations.
Содержание Power Xpert Plus 1
Страница 1: ...Power Xpert 9395 UPS and Plus 1 UPS 450 550 kVA Installation and Operation Manual...
Страница 193: ......
Страница 194: ...1642017013 164201701 3...