Model Numbers
The UPS is housed in a free‐standing cabinet with safety shields behind the door and
front panels. The UPS is available in 50 or 60 Hz with various output power ratings.
Models
Power Rating
Frequency
9395-550/450
450 kVA
50/60 Hz
Power Xpert 9395-550/500
500 kVA
50/60 Hz
Power Xpert 9395-550/550
550 kVA
50/60 Hz
10.2
Specifications
The following sections detail the input, output, battery, and environmental,
specifications for the UPS.
10.2.1
UPS Input
Operating Input Voltage
480 Vac
Operating Input Frequency Range
50/60 Hz
Operating Input Current
See Table 3‐4 on page 3-9, Table 3‐5 on page 3-10, or Table 3‐6 on
page 3-11.
Reduced for Generator
Adjustable
Input Current Harmonic Content
5% THD at full load
Power Factor
Minimum 0.99
Line Surges
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801‐4
Battery Voltage
480 Vdc
Battery Charging Capacity
Configurable per UPM at nominal line voltage:
Up to 120A with less than 85% load
Up to 80A with 100% load
Battery Shunt Trip
48 Vdc