UPS OPERATING INSTRUCTIONS
Power Xpert
9395 UPS (450–550 kVA) Installation and Operation Manual
164201701 Rev 3
www.eaton.com/powerquality
7-8
Table 7‐3. Display Menu Operation (continued)
Operation
Subfunction
Function
Com Port Selection
The Com Port Setup screen allows selection of the serial COM port to set up. Select
COM PORT
SETUP
from the System Setup Level 1 menu to display the COM Port Setup screen. Use the up or
down arrow pushbutton to highlight the COM port to be set up, then press the
SELECT
pushbutton
.
To return to the System Setup screen, press the return arrow pushbutton
.
Com Port Setup
The COM Setup screen is used to change and save the settings for the selected serial
communication port. The COM port number selected from the COM Port Setup screen displays.
If the changes are not wanted, use the
ABORT
pushbutton to return to the COM Port Setup
screen. Use the up or down arrow pushbutton to highlight the setting to be changed. Use the
return arrow pushbutton to toggle through the values for the setting to make the change. Press
SAVE
or
ABORT
. Once the action is completed, the COM Port Setup screen is displayed.
Controls
See paragraph 7.2.7 for details.
7.2.7
System Status Screen and Controls
Press the
CONTROLS
pushbutton on the main menu bar to display the System Status
screen. Online operation, transfer to bypass, charger control, UPM startup and
shutdown, and LOAD OFF commands are controlled through this screen. In addition,
the screen displays the current status of the UPS, indicates whether the UPS is in
Maintenance Bypass or Bypass, and displays the state of the UPM and battery
charger. Figure 7‐5 shows the System Status screen.
Use the or pushbutton on the System Status menu bar to highlight the
command screen desired, then press the
CONTROLS
pushbutton to display the
command menu screen.
Table 7‐4 lists the typical System Status Screen Messages that are displayed during
UPS operation.
Table 7‐5 describes the control functions and provides instructions to access and use
the command menu screens.
For detailed information about using the System Controls, see paragraph 7.3.
MAINTENANCE BYPASS
BYPASS
UPM: OFFLINE
SHUTDOWN
:
AVAILABLE
:
OFF
:
SYSTEM STATUS
CONTROLS
ESC
CHARGER
OFF
:
UPS
Figure 7‐5. Typical System Status Screen