UPS INSTALLATION PLAN AND UNPACKING
Power Xpert
9395 UPS (450–550 kVA) Installation and Operation Manual
164201701 Rev 3
www.eaton.com/powerquality
3-16
Table 3‐15. Recommended Bypass, Output, and MOB Circuit Breaker Ratings
UPS Model
Output Rating
Load Rating
400V
480V
9395-550/450
80% Rated
700A
700A
100% Rated
600A
600A
Power Xpert 9395-550/500
80% Rated
800A
800A
100% Rated
700A
700A
Power Xpert 9395-550/550
80% Rated
1000A
1000A
100% Rated
700A
700A
NOTE
Bypass breakers are not required for IOM configurations.
There is no manual DC disconnect device within the UPS.
A battery disconnect switch is recommended, and may be required by NEC or local
codes when batteries are remotely located. The battery disconnect switch should be
installed between the battery and the UPS.
External DC input overcurrent protection and disconnect switch for the remote
battery location is to be provided by the customer. Table 3‐16 lists the maximum
rating for continuous‐duty rated circuit breakers satisfying the criteria for both.
Recommended breaker size is based on a maximum full load discharge time less than
3 hours. For longer discharge times a larger breaker may be required.
Table 3‐16. Recommended DC Input Circuit Breaker Ratings
UPS Model
Input Rating
400V
480V
9395-550/450
1200A
1200A
Power Xpert 9395-550/500
1600A
1600A
Power Xpert 9395-550/550
1600A
1600A
Battery voltage is computed at 2 volts per cell as defined by Article 480 of the NEC.
Rated battery current is computed at 2 volts per cell.
The battery wiring used between the battery and the UPS should not allow a voltage
drop of more than 1% of nominal DC voltage at rated battery current.