UPS INSTALLATION PLAN AND UNPACKING
Power Xpert
9395 UPS (450–550 kVA) Installation and Operation Manual
164201701 Rev 3
www.eaton.com/powerquality
3-9
For external wiring requirements, including the minimum AWG size of external wiring,
see Table 3‐4 for common battery system installations, Table 3‐5 for separate battery
system installations, or Table 3‐6 for separate rectifier feed installations. Wire sizes
listed are for copper wiring only.
Table 3‐4. Input/Output Ratings and External Wiring Requirements for the 9395-550/450, 9395-550/500, and 9395-550/550 – Common Battery
Basic Unit Rating
Units
Rating 50/60 Hz
kVA
kW
450
409
450
409
500
455
500
455
550
500
550
500
Input and Output Voltage
Volts
400/400
480/480
400/400
480/480
400/400
480/480
AC Input to UPS Rectifier (0.98 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground
A
Amps
741
617
823
686
905
754
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
300
(4)
4/0
(3)
300
(4)
350
(3)
300
(4)
350
(3)
AC Input to UPS Bypass (Four Wire)
Full Load Current
(3) Phases, (1) Ground
B
Amps
650
541
722
601
794
662
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
350
(3)
4/0
(3)
350
(3)
4/0
(3)
350
(3)
350
(3)
AC Input to UPS Bypass (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
B
Amps
650
541
722
601
794
662
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(3)
250
(3)
500
(3)
300
(3)
500
(3)
300
(4)
DC Input from Each Battery Cabinet to UPS or Battery
Disconnect
(1) Positive, (1) Negative
C
Total Amps
902
902
1002
1002
1103
1103
Minimum Conductor Size
Number per Pole
AWG or kcmil
(each)
500
(1)
500
(1)
500
(1)
500
(1)
500
(1)
500
(1)
DC Input from Battery Disconnect to UPS
(1) Positive, (1) Negative
C
Total Amps
902
901
1002
1001
1103
1101
Minimum Conductor Size
Number per Pole
AWG or kcmil
(each)
350
(6)
400
(4)
350
(6)
350
(6)
350
(6)
350
(6)
AC Output to Critical Load (Four Wire)
Full Load Current
(3) Phases, (1) Ground
D
Amps
650
541
722
601
794
662
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
350
(3)
4/0
(3)
350
(3)
4/0
(3)
350
(3)
350
(3)
AC Output to Critical Load (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
D
Amps
650
541
722
601
794
662
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(3)
250
(3)
500
(3)
300
(3)
500
(3)
300
(4)
NOTE
Callout letters
A
,
B
,
C
, and
D
map to Figure 6‐6 or Figure 6‐8 starting on page 6-9. Callout letters
A
,
C
, and
D
map to Figure 6‐10 or Figure 6‐12
starting on page 6-13.
NOTE
Bypass wiring data is not applicable to IOM configurations.