XT SERIES INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
INSTALLATION
Dispersion:
DriSteem humidifi ers operate with several types of dispersion assemblies for
open spaces and for ducts and air handling units.
Dispersion assemblies in ducts and air handling units must be positioned where
the water vapor being discharged is carried off with the airstream and is
absorbed before it can cause condensation or dripping.
• In general, the dispersion assembly is best placed where the air can absorb
the moisture being added without causing con den sa tion at or after the unit.
This normally will be after the heating coil or where the air tem per a ture is
highest.
Selecting the dispersion assembly location