XT SERIES INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Rapid-sorb and Ultra-sorb with Models XTP 050 through 096
Models XTP 050 through XTP 096 have capacities requiring dispersion devices with condensate drains (Figure 35-1).
For these models, DriSteem recommends the following:
• Run separate steam tubing from each cylinder to the connection on the dispersion device.
• Pitch steam tubing toward the dispersion device.
The installer should not attempt to drain condensate back to the cylinder. When a vertical riser is required in the steam
tubing, a drip tee is required in order to eliminate a condensate collection point that will restrict steam fl ow.
OM-7982-XT
Pitch*
Pitch*
Drain
Drain
Drip tee
Pitch*
Pitch*
Drain
Rapid-sorb steam dispersion panel
Ultra-sorb steam dispersion panel
Dual-cylinder XT Series humidifi er
WARNING
Preventing back pressure in dual-cylinder humidifi ers
Read and follow all steam tubing installation instructions
for dual-cylinder humidifi ers. Failure to follow these
instructions could result in excessive back pressure and
the risk of equipment damage or severe personal injury.
Notes:
* Pitch 1/8"/ft (1%) minimum toward dispersion panel.
• See installation notes in Figure 25-1.
FIGURE 36-1: DUAL-CYLINDER XT SERIES HUMIDIFIER CONNECTED TO RAPID-SORB OR ULTRA-SORB WITH RISER DRIPS IN
STEAM SUPPLY LINES
INSTALLATION
Dispersion: