XT SERIES INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Product overview
SUPPLY WATER
There are benefi ts and trade-offs to consider when the application allows a
choice between hard and softened water:
Hard water: The benefi t of hard water is less frequent draining and fi lling
than with softened water, which results in better energy and water effi ciency
and more consistent steam output. However, cylinder replacement could
be more frequent with hard water, because hard water scale coats the
electrodes. The harder the water, the more frequent the need for a new
cylinder.
Softened water may be used in the XT series electrode humidifi er. However,
softened water ions stay in solution to much higher concentrations than
hard water ions. The result can be more frequent draining and fi lling, which
results in less energy and water effi ciency, and less consistent steam output.
While softened water can reduce scale build-up in the cylinder, it can also
shorten cylinder electrode life.
CONTROLLER
The Model XTP humidifi er Vapor-logic
®
controller features menus for all
humidifi er functions, with a Web interface for access to all functions via
Ethernet. See "Operations" beginning on page 45 for details.
* On-off switch for control board — not a safety shut-off to humidifi er power wiring.
XTP Vapor-logic keypad/display
Softkeys for direct
menu access
Navigation buttons
for item selection
Controller on-off switch*
Status display and
menu selection
FIGURE 3-1: XT SERIES HUMIDIFIER CONTROL PANEL
Table 3-1:
DriSteem supply water guidelines for
XT series electrode humidifiers
Supply water
conductivity
350 to 1250 μS/cm (roughly
comparable to water hardness
of 10 to 36 grains per gallon).
Chlorides
Not limited
pH
6.5 to 8.5
Silica
< 15 ppm
Demineralized
,
deionized
, and
reverse-
osmosis
water cannot be used.
Supply water outside of these guidelines may
void your DriSteem warranty. Please contact
your DriSteem Representative or DriSteem
Technical Support if you need advice.