XT SERIES INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Model XTP
START-UP PROCEDURE
After the Model XTP humidifi er is installed and connected properly:
1. Perform all applicable “Start-up checklist” items on Page 47.
2. Read and follow the instructions in the “Operation” section of the
Vapor-logic Installation and Operation Manual
.
3. Note: During start-up, do not leave the humidifier unattended.
4. Monitor humidifier operation through multiple drain and fill cycles.
5. Perform the cleaning procedure as follows:
a. Operate humidifi er long enough for steam to be produced.
b. Using the keypad/display:
– At the Main menu, select Tank Status, and press Enter.
– Select Mode, and press Enter.
– Select Drain, and press Enter.
– Let steam cylinder drain for 5 to 10 minutes until empty.
c. Restart the humidifi er, and repeat Steps a and b.
CAPACITY LIMITATION
Model XTP humidifi er capacity can be limited to a user-specifi ed maximum
using the keypad/display or Web interface. From the Main menu, select
Tank
Setup
, then select
Capacity Adjustment
for menu options.
WARNING
Electric shock hazard
Only qualifi ed electrical personnel
should perform start-up procedure.
Contact with energized circuits can
cause property damage, severe
personal injury or death as a result of
electrical shock or fi re.
Make sure cabinet doors are installed
before turning on electrical power.
For proper operation of safety interlock
switch, install electrical-side door fi rst,
then install cylinder-side door.
The
Vapor-logic In stal la tion and Op er a tion
Man u al
is a comprehensive operation manual.
Refer to it for information regarding the
following features:
• Keypad/display and Web interface setup
and menu information
• Control input signals and functions
• Safety features
• Alarm screens and fault messages
This manual ships with Model XTP
humidifi ers and is available at our website:
www.dristeem.com
OPERATION