52
XT SERIES INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Troubleshooting
DriSteem Technical Support
Have the following information ready when
calling Technical Support. See phone number
inside front cover of this manual.
Humidifi er model number
_______________________________
Humidifi er serial number
_______________________________
When issue began
_______________________________
_______________________________
_______________________________
Issue description
_______________________________
_______________________________
_______________________________
DRAIN VALVE ASSEMBLY MAINTENANCE
Perform the following procedure
only
if the procedure on Page 51 does not
resolve drain valve issues. See Figure 51-2.
1. Perform Steps 1 through 4 on Page 51.
2. Remove the three screws and washers securing drain cup plate to drain
cup.
3. Lift drain valve body/plate assembly off of drain cup.
4. Vacuum loose scale and debris out of drain cup.
5. Remove ground plate, and clean scale and debris from ground plate and
outlet of drain valve body.
6. Reassemble drain valve assembly: Fit mounting screws with washers, insert
them through drain cup plate, and tighten them into drain cup. See notes
in Figure 51-2.
7. Clean end of hose, and reconnect it to drain valve body with hose clamp.
Plug Molex plug into its mating wire harness plug.
8. See “Start-up procedure” on Page 48 if returning humidifier to
operation.
MODEL XTP TROUBLESHOOTING
Follow the procedure below to resolve issues with Model XTP humidifi ers:
1. Review possible causes and recommended actions in Table 54-1.
2. Follow the Test mode procedure beginning on Page 56.
The Test mode procedure is intended to check the general function of Model
XTP humidifi ers and components, and to help diagnose and resolve general
operational problems.
3. If Table 54-1 and the Test mode procedure do not help you solve the issue,
call DriSteem (see inset at right) with the following information available:
• Humidifi er model number and serial number (see nameplate on side of
the humidifi er and steam blower)
•
Issue description
Example: water leaking, low humidity, high humidity, etc.
• When issue began
Example: After maintenance, cylinder replacement, etc.
• System
changes
Example: Pressure, new service, new controller, relocation, change in
maintenance, etc.
MAINTENANCE