- 103 -
Cold Load Pickup Settings Menu
Cold Load Pickup (CLP) feature of CPM 310 G provides
the option to pull up delay times of desired protection
functions to enable easy pickup of machines and
systems with high pickup / inrush current without
protection relay intervention.
The cold load pickup operation starts when a
programmable input with
Start CLP
appointment
receives a signal. Once the CLP function is active, delay
times for the configured functions are multiplied by the
Level
parameter for the time determined by the
Time
parameter. Initialization by the
Start CLP
appointed
input can be achieved by cabling the input terminals to
a normally open auxiliary contact terminals of the
circuit breaker. See
Application Diagram 1
at p.194 of
this manual on the subject.
In order to utilize the cold load pickup function, one of
any programmable inputs should be programmed as
“Start CLP” and one of the normally open contacts of
the circuit breaker should be wired to that input. Once
these arrangements are complete,
Cold Load Pickup
function will start to operate to modify the protection
levels ONLY at the moment the circuit breaker is
closed, but not for disturbances that occur during
stable operating conditions.
The following scenario examines CPM 310 G’s cold load
pickup behavior:
Let the relay be set to I>> = 1.00 I
n
, DType = IEC
SI and TMS = 1.00.
Cold Load Pickup function is set as “Active”, Level =
%200, Time = 1.00 s and I>> = Active.
At the moment the circuit breaker is closed (“Start
CLP” input is activated) the I>> threshold will be
temporarily set to 2.00 I
n
instead of 1.00 I
n
.
Please pay attention to the following characteristics of
the function:
If any of the protection functions that is controlled by
the Cold Load Pickup function has DMT delay
characteristics, CLP will only modify the threshold
value, but not the trip delay time.
If any of the protection functions that is controlled by
the Cold Load Pickup function has IDMT delay
characteristics, CLP will modify both the threshold value
and the trip curve characteristics. For the scenario
above, if a current of 3 I
n
is measured within the active
CLP time; the ratio of (I/I
s
) will be treated as 1.5
instead of 3.0, as the
Level
parameter is set to %200.
Consequently, trip delay will be longer than normal.
↺
Main Screen » Menu »
Automatic Control Settings »
Cold Load Pickup
Содержание CPM 310 G
Страница 1: ...CPM 310 G Digital Overcurrent Protection Relay User Application Manual vEN 2016 03...
Страница 2: ...2...
Страница 6: ...6 ABOUT DEMA...
Страница 11: ...11 INTRODUCTION...
Страница 32: ...32 PACKING LABELING INFORMATION...
Страница 34: ...34 OPERATING MANUAL...
Страница 53: ...53 RELAY MENUS MANUAL...
Страница 55: ...55 The Menu Tree...
Страница 56: ...56...
Страница 57: ...57...
Страница 58: ...58...
Страница 59: ...59...
Страница 60: ...60...
Страница 61: ...61...
Страница 128: ...128 DIGICONNECT PC PROGRAM MANUAL...
Страница 189: ...189 APPLICATION DIAGRAMS...
Страница 191: ...191 Sample Power Transformer Protection Application Diagram...
Страница 193: ...193 FUNDAMENTAL CABLING DIAGRAM...
Страница 195: ...195 APPLICATION DIAGRAM NO 2 Function Function Activation Address Output Settings Internal Error Alarm Automatic...
Страница 203: ...203 APPLICATION DIAGRAM NO 10 RS485 Cabling...
Страница 204: ...204 TECHNICAL DATA...
Страница 220: ...220 GLOSSARY...