tCBF (CB Pole Failure Delay Time)
tCBF is the delay time counter limit value before alarming, which is triggered at the instant that the
trip signal is generated, and terminated if the primary circuit current drops below the threshold
current. The setting zone for the counter is (0.01 – 10) s in 10 ms steps. The default value for tCBF is
1.0 s, however, tCBF value is not recommended to exceed 100 ms if the function is to be used in
blocking logic selectivity schemes.
WARNING!
CB pole failure supervision function is to be used as a preventive function to inform the users of a
possible CB failure. The absence of failure alarm from this supervision function is not to be considered
as guaranteed successful operation of the circuit breaker! General safety rules and live working
principles apply! □
Содержание CPM 310 G
Страница 1: ...CPM 310 G Digital Overcurrent Protection Relay User Application Manual vEN 2016 03...
Страница 2: ...2...
Страница 6: ...6 ABOUT DEMA...
Страница 11: ...11 INTRODUCTION...
Страница 32: ...32 PACKING LABELING INFORMATION...
Страница 34: ...34 OPERATING MANUAL...
Страница 53: ...53 RELAY MENUS MANUAL...
Страница 55: ...55 The Menu Tree...
Страница 56: ...56...
Страница 57: ...57...
Страница 58: ...58...
Страница 59: ...59...
Страница 60: ...60...
Страница 61: ...61...
Страница 128: ...128 DIGICONNECT PC PROGRAM MANUAL...
Страница 189: ...189 APPLICATION DIAGRAMS...
Страница 191: ...191 Sample Power Transformer Protection Application Diagram...
Страница 193: ...193 FUNDAMENTAL CABLING DIAGRAM...
Страница 195: ...195 APPLICATION DIAGRAM NO 2 Function Function Activation Address Output Settings Internal Error Alarm Automatic...
Страница 203: ...203 APPLICATION DIAGRAM NO 10 RS485 Cabling...
Страница 204: ...204 TECHNICAL DATA...
Страница 220: ...220 GLOSSARY...