- 39 -
Terminal numbers and descriptions are given on the table below.
CPM 310 G Terminal Explanations
CAUTION!
The “Notes” columns on the table suggests a sample application and is not normative. “DC(+)” notes,
e.g., are given assuming that the circuit breaker, the power transformer and auxiliary devices are
cabled in the way that their common terminals are supplied with DC(-). If an application does not
correspond to the case here assumed, do not take the note columns into consideration and create the
actual cabling project required to provide the healthy operation of the system.
↺
Terminal No. Terminal Description
Notes
1
Programmable Input 1
-
2
Programmable Input 1, common terminal.DC (+)
3
Programmable Input 2
-
4
Programmable Input 2, common terminal.DC (+)
5
Programmable Input 3
-
6
Programmable Input 3, common terminal.DC (+)
7
Programmable Input 4
-
8
Programmable Input 4, common terminal.DC (+)
9
Programmable Input 5
-
10
Programmable Input 5, common terminal.DC (+)
11
Programmable Input 6
-
12
Programmable Input 6, common terminal.DC (+)
13
Programmable Input 7
-
14
Programmable Input 7, common terminal.DC (+)
15
Not used.
-
16
RS 485, 0VISO
Reference voltage.
17
RS 485, Termination Resistance.
-
18
RS 485, A terminal.
-
19
RS 485, B terminal.
-
20
Not used.
-
21
Auxiliary Supply Terminal
DC (-) or AC neutral.
22
Auxiliary Supply Terminal
DC (+) or AC phase.
23
Internal Circuit Earthing Terminal
-
24
Not used.
-
25
Current Input Terminal for Phase R
(1/5)A
26
Terminal for Current Bridge
-
27
Current Input Terminal for Phase S
(1/5)A
28
Terminal for Current Bridge
-
29
Current Input Terminal for Phase T
(1/5)A
30
Terminal for Current Bridge
-
31
Current Output Terminal for Neutral Point (1/5)A
32
Terminal for Current Bridge
-
33
Not used.
-
34
Trip signal common terminal
DC (+)
35
Trip signal N/C terminal
DC (+) out.
36
Trip signal N/O terminal
DC (+) out.
37
Watchdog common terminal
DC (+) or AC phase.
38
Watchdog N/C terminal
Alarm / Signal output.
39
Watchdog N/O terminal
Alarm / Signal output.
40
Programmable Output 1 Common TerminalDC (+)
41
Programmable Output 1 N/C Terminal
DC (+) out.
42
Programmable Output 1 N/O Terminal
DC (+) out.
43
Programmable Output 2 Common TerminalDC (+)
44
Programmable Output 2 N/C Terminal
DC (+) out.
45
Programmable Output 2 N/O Terminal
DC (+) out.
46
Programmable Output 3 Common TerminalDC (+)
47
Programmable Output 3 N/O Terminal
DC (+) out.
48
Programmable Output 4 Common TerminalDC (+)
49
Programmable Output 4 N/O Terminal
DC (+) out.
50
Programmable Output 5 Common TerminalDC (+)
51
Programmable Output 5 N/O Terminal
DC (+) out.
52
Programmable Output 6 Common TerminalDC (+)
53
Programmable Output 6 N/O Terminal
DC (+) out.
54
Not used.
55
Not used.
56
Not used.
57
Not used.
58
Not used.
Outputs
Inputs
RS 485
Auxiliary Supply and Earthing
Secondary Current Terminals
Содержание CPM 310 G
Страница 1: ...CPM 310 G Digital Overcurrent Protection Relay User Application Manual vEN 2016 03...
Страница 2: ...2...
Страница 6: ...6 ABOUT DEMA...
Страница 11: ...11 INTRODUCTION...
Страница 32: ...32 PACKING LABELING INFORMATION...
Страница 34: ...34 OPERATING MANUAL...
Страница 53: ...53 RELAY MENUS MANUAL...
Страница 55: ...55 The Menu Tree...
Страница 56: ...56...
Страница 57: ...57...
Страница 58: ...58...
Страница 59: ...59...
Страница 60: ...60...
Страница 61: ...61...
Страница 128: ...128 DIGICONNECT PC PROGRAM MANUAL...
Страница 189: ...189 APPLICATION DIAGRAMS...
Страница 191: ...191 Sample Power Transformer Protection Application Diagram...
Страница 193: ...193 FUNDAMENTAL CABLING DIAGRAM...
Страница 195: ...195 APPLICATION DIAGRAM NO 2 Function Function Activation Address Output Settings Internal Error Alarm Automatic...
Страница 203: ...203 APPLICATION DIAGRAM NO 10 RS485 Cabling...
Страница 204: ...204 TECHNICAL DATA...
Страница 220: ...220 GLOSSARY...