Thermal protection of the power transformer, and phase and earth protections are to be done.
Below calculations and settings are done for this purpose.
Making of Iθ> Thermal Overload Protection
Settings
It is assumed that the thermal constant for the power transformer is Te = 20 minutes
according to the information supplied by the manufacturer. Take trip threshold translation
constant k as 1.10, thermal overload trip heating as %ΘTrip = %100 and thermal
overload alarm heating as %ΘAlarm = %80.
Power transformer nominal current is:
𝐼
𝑟𝑇𝑅
=
𝑆
𝑟𝑇𝑅
√3 × 𝑈
𝑛
=
2500 𝑘𝑉 ∙ 𝐴
√3 × 34.5 𝑘𝑉
≅ 41.84 𝐴
Power transformer nominal current / Protection CT primary nominal current ratio:
𝐼
rTR
=
41.84 𝐴
60 𝐴
≅ 0.70 𝐼
𝑛
Make the setting below so as to activate thermal overload protection at 1.00 I
rTR
:
Making of I> Phase Overcurrent Protection Settings
a.
Around 1.00 I
rTR
, the PT is protected from overloads. Setting I> threshold at 1.3 I
rTR
is
suitable according to the PT ratings. Threshold set current in terms of I
n
of CT:
𝐼 > = 1.3 × 𝐼
𝑟𝑇𝑅
≅ 0.91 𝐼
𝑛
b.
According to the calculation above, do the following settings:
↺
Notes:
If there are loads of high inrush pick-up current, fine adjustment of the TMS parameter
might be needed.
If the Thermal Overload Protection is not applied / made passive, set the I> (Phase
Overcurrent Protection Threshold) as 1.0 I
rTR
(0.70 I
n
) instead of 1.3 I
rTR
(0.91 I
n
).
Main Screen » Set » I
Θ
>
Main Screen » Set » I>
Содержание CPM 310 G
Страница 1: ...CPM 310 G Digital Overcurrent Protection Relay User Application Manual vEN 2016 03...
Страница 2: ...2...
Страница 6: ...6 ABOUT DEMA...
Страница 11: ...11 INTRODUCTION...
Страница 32: ...32 PACKING LABELING INFORMATION...
Страница 34: ...34 OPERATING MANUAL...
Страница 53: ...53 RELAY MENUS MANUAL...
Страница 55: ...55 The Menu Tree...
Страница 56: ...56...
Страница 57: ...57...
Страница 58: ...58...
Страница 59: ...59...
Страница 60: ...60...
Страница 61: ...61...
Страница 128: ...128 DIGICONNECT PC PROGRAM MANUAL...
Страница 189: ...189 APPLICATION DIAGRAMS...
Страница 191: ...191 Sample Power Transformer Protection Application Diagram...
Страница 193: ...193 FUNDAMENTAL CABLING DIAGRAM...
Страница 195: ...195 APPLICATION DIAGRAM NO 2 Function Function Activation Address Output Settings Internal Error Alarm Automatic...
Страница 203: ...203 APPLICATION DIAGRAM NO 10 RS485 Cabling...
Страница 204: ...204 TECHNICAL DATA...
Страница 220: ...220 GLOSSARY...