- 214 -
Default Settings
Default Settings
Default Settings
Protection
Active
Protection
Passive
I> (Threshold)
1.00 I
n
I2> (Threshold)
0.5 I
n
Delay Type
IEC SI
Delay Type
DMT
tI>
0.4
tI
2
>
5.0 s
Reset Type
DMT
Reset Type
DMT
tReset
0.04 s
tReset
0.04 s
Protection
Active
Protection
Passive
I>> (Threshold)
5.00 I
n
I2> (Threshold)
2.0 I
n
Delay Type
DMT
Delay Type
DMT
tI>>
0.05 s
tI
2
>
0.2 s
Reset Type
DMT
Reset Type
DMT
tReset
0.04 s
tReset
0.04 s
Protection
Passive
Protection
Passive
I>>> (Threshold)
10.00 I
n
Iθ> (Threshold)
1.0 I
n
Delay Type
DMT
T
e
20 min
tI>>>
0.01 s
k
1.1
Reset Type
DMT
Trip θ
100%
tReset
0.04 s
Alarm θ
Active
Alarm θ Threshold
80%
Protection
Passive
I< (Threshold)
0.5 I
n
tI<
1.0 s
Protection
Active
Protection
Active
I> (Threshold)
1.00 I
n
Ie> (Threshold)
0.25 I
en
Delay Type
IEC SI
Delay Type
DMT
tI>
0.4
tI
e
>
1.00 s
Reset Type
DMT
Reset Type
DMT
tReset
0.04 s
tReset
0.04 s
Protection
Active
Protection
Active
I>> (Threshold)
5.00 I
n
Ie>> (Threshold)
0.75 I
en
Delay Type
DMT
Delay Type
DMT
tI>>
0.05 s
tI
e
>>
0.05 s
Reset Type
DMT
Reset Type
DMT
tReset
0.04 s
tReset
0.04 s
Protection
Passive
Protection
Passive
I>>> (Threshold)
10.00 I
n
Ie>>> (Threshold)
1.00 I
en
Delay Type
DMT
Delay Type
DMT
tI>>>
0.01s
tI
e
>>>
0.05 s
Reset Type
DMT
Reset Type
DMT
tReset
0.04 s
tReset
0.04 s
Protection
Passive
Protection
Passive
I< (Threshold)
0.5 I
n
%(I2/I1)> (Threshold)
20%
tI<
1.0 s
t%(I
2
/I
1
)>
5.0 s
Protection Settings, Group 1
Phase Overcurrent, I> (ANSI 50/51)
Phase Overcurrent, I>> (ANSI 50/51)
Phase Overcurrent, I>>> (ANSI 50/51)
Phase Undercurrent, I<
Earth Overcurrent, Ie> (ANSI 50N/51N)
Earth Overcurrent, Ie>> (ANSI 50N/51N)
Earth Overcurrent, Ie>>> (ANSI 50N/51N)
Broken Conductor, %(I2/I1)>
Phase Undercurrent, I<
Protection Settings, Group 1 (Continued)
Negative Sequence Overcurrent, I2> (ANSI 46)
Negative Sequence Overcurrent, I2>> (ANSI 46)
Thermal Overload, Iθ> (ANSI 49)
Phase Overcurrent, I> (ANSI 50/51)
Phase Overcurrent, I>> (ANSI 50/51)
Phase Overcurrent, I>>> (ANSI 50/51)
Protection Settings, Group 2 (Settings are the same with
Group 1)
Содержание CPM 310 G
Страница 1: ...CPM 310 G Digital Overcurrent Protection Relay User Application Manual vEN 2016 03...
Страница 2: ...2...
Страница 6: ...6 ABOUT DEMA...
Страница 11: ...11 INTRODUCTION...
Страница 32: ...32 PACKING LABELING INFORMATION...
Страница 34: ...34 OPERATING MANUAL...
Страница 53: ...53 RELAY MENUS MANUAL...
Страница 55: ...55 The Menu Tree...
Страница 56: ...56...
Страница 57: ...57...
Страница 58: ...58...
Страница 59: ...59...
Страница 60: ...60...
Страница 61: ...61...
Страница 128: ...128 DIGICONNECT PC PROGRAM MANUAL...
Страница 189: ...189 APPLICATION DIAGRAMS...
Страница 191: ...191 Sample Power Transformer Protection Application Diagram...
Страница 193: ...193 FUNDAMENTAL CABLING DIAGRAM...
Страница 195: ...195 APPLICATION DIAGRAM NO 2 Function Function Activation Address Output Settings Internal Error Alarm Automatic...
Страница 203: ...203 APPLICATION DIAGRAM NO 10 RS485 Cabling...
Страница 204: ...204 TECHNICAL DATA...
Страница 220: ...220 GLOSSARY...