- 161 -
Settings
» Automatic Control Settings »
Output Relay Settings
A.
Output Relay Settings
window is accessed by clicking the
Output Relay Settings
button in the
Automatic
Control Settings
window.
B.
Save to Buffer
button sends the parameter changes to the DigiConnect buffer. When changes are to be
applied to CPM 310 G unit,
Save to Device
button must be utilized, which is located under the
Buffer
tab.
1.
On the very left of these columns; thresholds (e.g. I> and I
e
>), time delay protection functions (e.g. tI> and
tI
e
>), function status (e.g.
ARCL running
) and CB control functions (e.g.
trip
and
close
) are listed; to the right
of this list, current appointments are indicated in columns of boxes, each aligned to the related output
numbers. According to the sample picture above,
trip
function is appointed to 1
st
programmable output.
2.
These boxes let the user to assign or cancel assignment of functions to each of the programmable outputs.
Note that it is possible both to assign more than one function to a single output, and to assign a single
function to more than one outputs.
3.
This area is the continuation of the first and second areas, which were just studied on the previous
paragraphs. On the above sample window, it is observed that
CB Close
function is appointed to output
no.3.
□
Содержание CPM 310 G
Страница 1: ...CPM 310 G Digital Overcurrent Protection Relay User Application Manual vEN 2016 03...
Страница 2: ...2...
Страница 6: ...6 ABOUT DEMA...
Страница 11: ...11 INTRODUCTION...
Страница 32: ...32 PACKING LABELING INFORMATION...
Страница 34: ...34 OPERATING MANUAL...
Страница 53: ...53 RELAY MENUS MANUAL...
Страница 55: ...55 The Menu Tree...
Страница 56: ...56...
Страница 57: ...57...
Страница 58: ...58...
Страница 59: ...59...
Страница 60: ...60...
Страница 61: ...61...
Страница 128: ...128 DIGICONNECT PC PROGRAM MANUAL...
Страница 189: ...189 APPLICATION DIAGRAMS...
Страница 191: ...191 Sample Power Transformer Protection Application Diagram...
Страница 193: ...193 FUNDAMENTAL CABLING DIAGRAM...
Страница 195: ...195 APPLICATION DIAGRAM NO 2 Function Function Activation Address Output Settings Internal Error Alarm Automatic...
Страница 203: ...203 APPLICATION DIAGRAM NO 10 RS485 Cabling...
Страница 204: ...204 TECHNICAL DATA...
Страница 220: ...220 GLOSSARY...