- 124 -
Outputs that can be latched are listed below:
1.
TRIP
CB Trip Output; via settings of the 13
protection functions above.
2.
RL1
Programmable Output 1.
3.
RL2
Programmable Output 2.
4.
RL3
Programmable Output 3.
5.
RL4
Programmable Output 4.
6.
RL5
Programmable Output 5.
7.
RL6
Programmable Output 6.
When configuring the latch settings, the following point
must be considered.
A.
If a programmable output is appointed to the Trip
Relay, the latching of the programmable output will
result also in the latching of the Trip Relay.
B.
If the tripping function is appointed to any of the
programmable output relays, a Trip Relay latching
action will result also in the latching of those
programmable outputs.
WARNINGS & NOTES:
If the auto-recloser function is activated on a unit
with active latch settings, all latch settings will be set
out of service (set to Passive) instantly.
When the
Trip Relay
is set to latch when activated,
the circuit breaker will not be able to close successfully
neither by remote nor by manual commands before
resetting the latched
Trip Relay
; if such a case is
confronted, keep in mind that the
Trip Relay
latch
MUST BE RESET before closing the CB.
The latched programmable output relays (RL1 – RL6)
can be reset by triggering a “RL1 – RL6 Reset”
programmed input. □
Содержание CPM 310 G
Страница 1: ...CPM 310 G Digital Overcurrent Protection Relay User Application Manual vEN 2016 03...
Страница 2: ...2...
Страница 6: ...6 ABOUT DEMA...
Страница 11: ...11 INTRODUCTION...
Страница 32: ...32 PACKING LABELING INFORMATION...
Страница 34: ...34 OPERATING MANUAL...
Страница 53: ...53 RELAY MENUS MANUAL...
Страница 55: ...55 The Menu Tree...
Страница 56: ...56...
Страница 57: ...57...
Страница 58: ...58...
Страница 59: ...59...
Страница 60: ...60...
Страница 61: ...61...
Страница 128: ...128 DIGICONNECT PC PROGRAM MANUAL...
Страница 189: ...189 APPLICATION DIAGRAMS...
Страница 191: ...191 Sample Power Transformer Protection Application Diagram...
Страница 193: ...193 FUNDAMENTAL CABLING DIAGRAM...
Страница 195: ...195 APPLICATION DIAGRAM NO 2 Function Function Activation Address Output Settings Internal Error Alarm Automatic...
Страница 203: ...203 APPLICATION DIAGRAM NO 10 RS485 Cabling...
Страница 204: ...204 TECHNICAL DATA...
Страница 220: ...220 GLOSSARY...