- 90 -
Thermal
Θ Measurements Menu
Thermal Θ Measurements Menu
displays the heating
percentage of the system being watched in
percentages.
Thermal Θ is evaluated according to the IEC
formulations; the actual formula is given below.
𝒕 = 𝑻
𝒆
×
𝐥𝐨𝐠𝒆
[
|(
𝑰
𝒌 × 𝑰
𝚯
)
𝟐
− %𝚯
𝒑
|
|(
𝑰
𝒌 × 𝑰
𝚯
)
𝟐
− %𝚯
𝒕𝒓𝒊𝒑
|
]
Where,
t
trip delay (minutes),
T
e
thermal constant (minutes),
I
load current (A),
I
Θ
set current (A),
k
trip threshold translation constant (-),
%Θ
P
preheating percentage (%),
%Θ
trip
heating trip percentage (%).
Thermal Θ measurement, alarming and protection are
important functions for machines and systems where
the actual conductor heating cannot be partially or
entirely measured by direct means, or where
overcurrent protection cannot provide the sensitive
protection characteristics needed around lower current
value limits.
Thermal Θ measurement, alarming and protection are
the essential functions of modern electrical protection
systems and have unique functionalities, therefor
cannot be replaced by other functions.
Note that the percentages refer to the allowed
maximum thermal loading, which is determined by the
manufacturer or characteristics of the
machines/conductors being protected. □
Main Screen » Menu »
Measurements » Thermal Θ
Содержание CPM 310 G
Страница 1: ...CPM 310 G Digital Overcurrent Protection Relay User Application Manual vEN 2016 03...
Страница 2: ...2...
Страница 6: ...6 ABOUT DEMA...
Страница 11: ...11 INTRODUCTION...
Страница 32: ...32 PACKING LABELING INFORMATION...
Страница 34: ...34 OPERATING MANUAL...
Страница 53: ...53 RELAY MENUS MANUAL...
Страница 55: ...55 The Menu Tree...
Страница 56: ...56...
Страница 57: ...57...
Страница 58: ...58...
Страница 59: ...59...
Страница 60: ...60...
Страница 61: ...61...
Страница 128: ...128 DIGICONNECT PC PROGRAM MANUAL...
Страница 189: ...189 APPLICATION DIAGRAMS...
Страница 191: ...191 Sample Power Transformer Protection Application Diagram...
Страница 193: ...193 FUNDAMENTAL CABLING DIAGRAM...
Страница 195: ...195 APPLICATION DIAGRAM NO 2 Function Function Activation Address Output Settings Internal Error Alarm Automatic...
Страница 203: ...203 APPLICATION DIAGRAM NO 10 RS485 Cabling...
Страница 204: ...204 TECHNICAL DATA...
Страница 220: ...220 GLOSSARY...