6.3.10 9-** Profibus
Par.
No. #
Parameter description
Default value
(SR = Size related)
4 set-up
Change during
operation
Conver-
sion index
Type
9-00
Setpoint
0 N/A
All set-ups
TRUE
0
Uint16
9-07
Actual Value
0 N/A
All set-ups
FALSE
0
Uint16
9-15
PCD Write Configuration
ExpressionLimit
2 set-ups
TRUE
-
Uint16
9-16
PCD Read Configuration
ExpressionLimit
2 set-ups
TRUE
-
Uint16
9-18
Node Address
126 N/A
1 set-up
TRUE
0
Uint8
9-22
Telegram Selection
[108] PPO 8
1 set-up
TRUE
-
Uint8
9-23
Parameters for Signals
0
All set-ups
TRUE
-
Uint16
9-27
Parameter Edit
[1] Enabled
2 set-ups
FALSE
-
Uint16
9-28
Process Control
[1] Enable cyclic master
2 set-ups
FALSE
-
Uint8
9-44
Fault Message Counter
0 N/A
All set-ups
TRUE
0
Uint16
9-45
Fault Code
0 N/A
All set-ups
TRUE
0
Uint16
9-47
Fault Number
0 N/A
All set-ups
TRUE
0
Uint16
9-52
Fault Situation Counter
0 N/A
All set-ups
TRUE
0
Uint16
9-53
Profibus Warning Word
0 N/A
All set-ups
TRUE
0
V2
9-63
Actual Baud Rate
[255] No baud rate found
All set-ups
TRUE
-
Uint8
9-64
Device Identification
0 N/A
All set-ups
TRUE
0
Uint16
9-65
Profile Number
0 N/A
All set-ups
TRUE
0
OctStr[2]
9-67
Control Word 1
0 N/A
All set-ups
TRUE
0
V2
9-68
Status Word 1
0 N/A
All set-ups
TRUE
0
V2
9-71
Profibus Save Data Values
[0] Off
All set-ups
TRUE
-
Uint8
9-72
ProfibusDriveReset
[0] No action
1 set-up
FALSE
-
Uint8
9-80
Defined Parameters (1)
0 N/A
All set-ups
FALSE
0
Uint16
9-81
Defined Parameters (2)
0 N/A
All set-ups
FALSE
0
Uint16
9-82
Defined Parameters (3)
0 N/A
All set-ups
FALSE
0
Uint16
9-83
Defined Parameters (4)
0 N/A
All set-ups
FALSE
0
Uint16
9-84
Defined Parameters (5)
0 N/A
All set-ups
FALSE
0
Uint16
9-90
Changed Parameters (1)
0 N/A
All set-ups
FALSE
0
Uint16
9-91
Changed Parameters (2)
0 N/A
All set-ups
FALSE
0
Uint16
9-92
Changed Parameters (3)
0 N/A
All set-ups
FALSE
0
Uint16
9-93
Changed Parameters (4)
0 N/A
All set-ups
FALSE
0
Uint16
9-94
Changed parameters (5)
0 N/A
All set-ups
FALSE
0
Uint16
6.3.11 10-** CAN Fieldbus
Par.
No. #
Parameter description
Default value
(SR = Size related)
4 set-up
Change dur-
ing operation
Conver-
sion index
Type
10-0* Common Settings
10-00 CAN Protocol
null
2 set-ups
FALSE
-
Uint8
10-01 Baud Rate Select
null
2 set-ups
TRUE
-
Uint8
10-02 MAC ID
ExpressionLimit
2 set-ups
TRUE
0
Uint8
10-05 Readout Transmit Error Counter
0 N/A
All set-ups
TRUE
0
Uint8
10-06 Readout Receive Error Counter
0 N/A
All set-ups
TRUE
0
Uint8
10-07 Readout Bus Off Counter
0 N/A
All set-ups
TRUE
0
Uint8
10-1* DeviceNet
10-10 Process Data Type Selection
null
All set-ups
TRUE
-
Uint8
10-11 Process Data Config Write
ExpressionLimit
2 set-ups
TRUE
-
Uint16
10-12 Process Data Config Read
ExpressionLimit
2 set-ups
TRUE
-
Uint16
10-13 Warning Parameter
0 N/A
All set-ups
TRUE
0
Uint16
10-14 Net Reference
[0] Off
2 set-ups
TRUE
-
Uint8
10-15 Net Control
[0] Off
2 set-ups
TRUE
-
Uint8
10-2* COS Filters
10-20 COS Filter 1
0 N/A
All set-ups
FALSE
0
Uint16
10-21 COS Filter 2
0 N/A
All set-ups
FALSE
0
Uint16
10-22 COS Filter 3
0 N/A
All set-ups
FALSE
0
Uint16
10-23 COS Filter 4
0 N/A
All set-ups
FALSE
0
Uint16
10-3* Parameter Access
10-30 Array Index
0 N/A
2 set-ups
TRUE
0
Uint8
10-31 Store Data Values
[0] Off
All set-ups
TRUE
-
Uint8
10-32 Devicenet Revision
0 N/A
All set-ups
TRUE
0
Uint16
10-33 Store Always
[0] Off
1 set-up
TRUE
-
Uint8
10-34 DeviceNet Product Code
120 N/A
1 set-up
TRUE
0
Uint16
10-39 Devicenet F Parameters
0 N/A
All set-ups
TRUE
0
Uint32
VLT HVAC Low Harmonic Drive Instruction
Manual
6 How to Program the Low Harmonic Drive
MG.16.A1.22 - VLT
®
is a registered Danfoss trademark
6-51