8.2 Filter Specifications
Frame size
D
E
F
Voltage [V]
380 - 480
380 - 480
380 - 480
Current, RMS [A]
120
210
330
Nominal value
Peak Current [A]
340
595
935
Amplitude value of the current
RMS overload [%]
No Overload
60 seconds in 10 min
Response time [ms]
< 0.5
Settling time - reactive current control
[ms]
< 40
Settling time - harmonic current control
(filtering) [ms]
< 20
Overshoot - reactive current control [%]
< 20
Overshoot - harmonic current control
[%]
< 10
Table 8.1: Power Ranges (LHD with AF)
8 General Specifications
VLT HVAC Low Harmonic Drive Instruction
Manual
8-8
MG.16.A1.22 - VLT
®
is a registered Danfoss trademark