4.6.14 Fuses
Branch circuit protection:
In order to protect the installation against electrical and fire hazard, all branch circuits in an installation, switch gear, machines, etc., must be short-
circuited and overcurrent protected according to national/international regulations.
Short-circuit protection:
The adjustable frequency drive must be protected against short-circuit to avoid electrical or fire hazard. Danfoss recommends using the fuses mentioned
below to protect service personnel and equipment in case of an internal failure in the drive. The adjustable frequency drive provides full short-circuit
protection in case of a short-circuit on the motor output.
Overcurrent protection
Provide overload protection to avoid fire hazard due to overheating of the cables in the installation. The adjustable frequency drive is equipped with
internal overcurrent protection that can be used for upstream overload protection (UL applications excluded). See par. F-43
Current Limit
. Moreover,
fuses or circuit breakers can be used to provide the overcurrent protection in the installation. Overcurrent protection must always be carried out according
to national regulations.
Non-UL compliance
If UL/cUL is not to be complied with, we recommend using the following fuses, which will ensure compliance with EN50178:
P160 - P250
380–480 V
type gG
P315 - P450
380–480 V
type gR
UL Compliance
380–480 V, frame sizes D, E and F
The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical), 240 V, or 480 V, or 500 V, or 600 V depending on
the drive voltage rating. With the proper fusing, the drive Short Circuit Current Rating (SCCR) is 100,000 Arms.
Size/
Type
Bussmann
E1958
JFHR2**
Bussmann
E4273
T/JDDZ**
SIBA
E180276
JFHR2
LittelFuse
E71611
JFHR2**
Ferraz-
Shawmut
E60314
JFHR2**
Bussmann
E4274
H/JDDZ**
Bussmann
E125085
JFHR2*
Internal
Option
Bussmann
P160
FWH-
400
JJS-
400
2061032.40
L50S-400
A50-P400
NOS-
400
170M4012
170M4016
P200
FWH-
500
JJS-
500
2061032.50
L50S-500
A50-P500
NOS-
500
170M4014
170M4016
P250
FWH-
600
JJS-
600
2062032.63
L50S-600
A50-P600
NOS-
600
170M4016
170M4016
Table 4.3: Frame size D, Line fuses, 380–480 V
Size/Type
Bussmann PN*
Rating
Ferraz
Siba
P315
170M4017
700 A, 700 V
6.9URD31D08A0700
20 610 32.700
P355
170M6013
900 A, 700 V
6.9URD33D08A0900
20 630 32.900
P400
170M6013
900 A, 700 V
6.9URD33D08A0900
20 630 32.900
P450
170M6013
900 A, 700 V
6.9URD33D08A0900
20 630 32.900
Table 4.4: Frame size E, Line fuses, 380–480 V
Size/Type
Bussmann PN*
Rating
Siba
Internal Bussmann Option
P500
170M7081
1600 A, 700 V
20 695 32.1600
170M7082
P560
170M7081
1600 A, 700 V
20 695 32.1600
170M7082
P630
170M7082
2000 A, 700 V
20 695 32.2000
170M7082
P710
170M7082
2000 A, 700 V
20 695 32.2000
170M7082
Table 4.5: Frame size F, Line fuses, 380–480 V