6-10 Terminal 53 Low Voltage
Range:
Function:
0.07 V*
[Application dependant]
Enter the low voltage value. This analog input scaling value should correspond to the low reference/
feedback value set in par. 6-14
Terminal 53 Low Ref./Feedb. Value
6-11 Terminal 53 High Voltage
Range:
Function:
10.00 V*
[Application dependant]
Enter the high voltage value. This analog input scaling value should correspond to the high refer-
ence/feedback value set in par. 6-15
Terminal 53 High Ref./Feedb. Value
6-14 Terminal 53 Low Ref./Feedb. Value
Range:
Function:
0.000*
[-999999.999 - 999999.999 ]
Enter the analog input scaling value that corresponds to the low voltage/low current set in
par. 6-10
and par. 6-12
Terminal 53 Low Current
.
6-15 Terminal 53 High Ref./Feedb. Value
Range:
Function:
Application
dependent*
[-999999.999 - 999999.999 ]
6-16 Terminal 53 Filter Time Constant
Range:
Function:
0.001 s*
[0.001 - 10.000 s]
Enter the time constant. This is a first-order digital low pass filter time constant for suppressing
electrical noise in terminal 53. A high time constant value improves dampening but also increases
the time delay through the filter.
This parameter cannot be adjusted while the motor is running.
6 How to Program the Low Harmonic Drive
VLT HVAC Low Harmonic Drive Instruction
Manual
6-26