7.5 Examples
7.5.1 Writing a Parameter Value
Change par. 4-14
to 100 Hz.
Write the data in EEPROM.
PKE = E19E Hex - Write single word in par. 4-14
IND = 0000 Hex
PWEHIGH = 0000 Hex
PWELOW = 03E8 Hex - Data value 1000, corresponding to 100 Hz, see
Conversion.
The message will look like this:
is a single word, and the
parameter command for write in EEPROM is “E”. Parameter number 4-14
is 19E in hexadecimal.
The response from the slave to the master will be:
7.5.2 Reading a Parameter Value
Read the value in par. 3-41
PKE = 1155 Hex - Read parameter value in par. 3-41
IND = 0000 Hex
PWEHIGH = 0000 Hex
PWELOW = 0000 Hex
If the value in par. 3-41
is 10 s, the response from
the slave to the master will be:
3E8 Hex corresponds to 1000 decimal. The conversion index for par. 3-41
is -2, i.e., 0.01.
Unsigned 32
.