6.3.3 1-** Load / Motor
Par.
No. #
Parameter description
Default value
(SR = Size related)
4 set-up
Change dur-
ing operation
Conver-
sion index
Type
1-0* General Settings
1-00
Configuration Mode
null
All set-ups
TRUE
-
Uint8
1-03
Torque Characteristics
[3] Auto Energy Optim. VT
All set-ups
TRUE
-
Uint8
1-06
Clockwise Direction
[0] Normal
All set-ups
FALSE
-
Uint8
1-2* Motor Data
1-20
Motor Power [kW]
ExpressionLimit
All set-ups
FALSE
1
Uint32
1-21
Motor Power [HP]
ExpressionLimit
All set-ups
FALSE
-2
Uint32
1-22
Motor Voltage
ExpressionLimit
All set-ups
FALSE
0
Uint16
1-23
Motor Frequency
ExpressionLimit
All set-ups
FALSE
0
Uint16
1-24
Motor Current
ExpressionLimit
All set-ups
FALSE
-2
Uint32
1-25
Motor Nominal Speed
ExpressionLimit
All set-ups
FALSE
67
Uint16
1-28
Motor Rotation Check
[0] OFF
All set-ups
FALSE
-
Uint8
1-29
Automatic Motor Adaptation (AMA)
[0] Off
All set-ups
FALSE
-
Uint8
1-3* Addl. Motor Data
1-30
Stator Resistance (Rs)
ExpressionLimit
All set-ups
FALSE
-4
Uint32
1-31
Rotor Resistance (Rr)
ExpressionLimit
All set-ups
FALSE
-4
Uint32
1-35
Main Reactance (Xh)
ExpressionLimit
All set-ups
FALSE
-4
Uint32
1-36
Iron Loss Resistance (Rfe)
ExpressionLimit
All set-ups
FALSE
-3
Uint32
1-39
Motor Poles
ExpressionLimit
All set-ups
FALSE
0
Uint8
1-5* Load-Indep. Setting
1-50
Motor Magnetization at Zero Speed
100 %
All set-ups
TRUE
0
Uint16
1-51
Min Speed Normal Magnetizing [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
1-52
Min Speed Normal Magnetizing [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
1-58
Flystart Test Pulses Current
30 %
All set-ups
FALSE
0
Uint16
1-59
Flystart Test Pulses Frequency
200 %
All set-ups
FALSE
0
Uint16
1-6* Load-Depend. Settg.
1-60
Low Speed Load Compensation
100 %
All set-ups
TRUE
0
Int16
1-61
High Speed Load Compensation
100 %
All set-ups
TRUE
0
Int16
1-62
Slip Compensation
0 %
All set-ups
TRUE
0
Int16
1-63
Slip Compensation Time Constant
ExpressionLimit
All set-ups
TRUE
-2
Uint16
1-64
Resonance Dampening
100 %
All set-ups
TRUE
0
Uint16
1-65
Resonance Dampening Time Constant
5 ms
All set-ups
TRUE
-3
Uint8
1-7* Start Adjustments
1-71
Start Delay
0.0 s
All set-ups
TRUE
-1
Uint16
1-73
Flying Start
[0] Disabled
All set-ups
TRUE
-
Uint8
1-77
Compressor Start Max Speed [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
1-78
Compressor Start Max Speed [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
1-79
Compressor Start Max Time to Trip
5.0 s
All set-ups
TRUE
-1
Uint8
1-8* Stop Adjustments
1-80
Function at Stop
[0] Coast
All set-ups
TRUE
-
Uint8
1-81
Min Speed for Function at Stop [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
1-82
Min Speed for Function at Stop [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
1-86
Trip Speed Low [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
1-87
Trip Speed Low [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
1-9* Motor Temperature
1-90
Motor Thermal Protection
[4] ETR trip 1
All set-ups
TRUE
-
Uint8
1-91
Motor External Fan
[0] No
All set-ups
TRUE
-
Uint16
1-93
Thermistor Source
[0] None
All set-ups
TRUE
-
Uint8
VLT HVAC Low Harmonic Drive Instruction
Manual
6 How to Program the Low Harmonic Drive
MG.16.A1.22 - VLT
®
is a registered Danfoss trademark
6-45