6-50 Terminal 42 Output
Option:
Function:
Select the function of Terminal 42 as an analog current output. A motor current of 20 mA corre-
sponds to I
max
.
[0] *
No operation
[100]
Output freq. 0-100
0–100 Hz, (0–20 mA)
[101]
Reference Min-Max
Minimum reference - Maximum reference, (0–20 mA)
[102]
Fe-200%
-200% to +200% of par. 20-14
Maximum Reference/Feedb.
, (0–20 mA)
[103]
Motor cur. 0-Imax
0 - Inverter Max. Current (par. 16-37
Inv. Max. Current
), (0–20 mA)
[104]
Torque 0-Tlim
0 - Torque limit (par. 4-16
Torque Limit Motor Mode
), (0–20 mA)
[105]
Torque 0-Tnom
0 - Motor rated torque, (0–20 mA)
[106]
Power 0-Pnom
0 - Motor rated power, (0–20 mA)
[107] *
Speed 0-HighLim
0 - Speed High Limit (par. 4-13
), (0–20 mA)
[113]
Ext. Closed-loop 1
0–100%, (0–20 mA)
[114]
Ext. Closed-loop 2
0–100%, (0–20 mA)
[115]
Ext. Closed-loop 3
0–100%, (0–20 mA)
[130]
Out fr 0-100 4-20
0–100 Hz
[131]
Reference 4-20mA
Minimum Reference - Maximum Reference
[132]
Feedback 4-20mA
-200% to +200% of par. 20-14
Maximum Reference/Feedb.
[133]
Motor cur. 4-20mA
0 - Inverter Max. Current (par. 16-37
Inv. Max. Current
)
[134]
Torq.0-lim 4-20mA
0 - Torque limit (par. 4-16
Torque Limit Motor Mode
)
[135]
Torq.0-nom 4-20mA
0 - Motor rated torque
[136]
Power 4-20mA
0 - Motor rated power
[137]
Speed 4-20mA
0 - Speed High Limit (4-13 and 4-14)
[139]
Bus ctrl.
0–100%, (0–20 mA)
[140]
Bus ctrl. 4-20 mA
0 - 100%
[141]
Bus ctrl t.o.
0–100%, (0–20 mA)
[142]
Bus ctrl 4-20mA t.o.
0 - 100%
[143]
Ext. CL 1 4-20 mA
0 - 100%
[144]
Ext. CL 2 4-20 mA
0 - 100%
[145]
Ext. CL 3 4-20 mA
0 - 100%
NOTE!
Values for setting the minimum reference are found in open-loop par. 3-02
and for closed-loop par. 20-13
Minimum Reference/
Feedb.
- values for maximum reference for open-loop are found in par. 3-03
and for closed-loop par. 20-14
Maximum Reference/
Feedb.
.
6 How to Program the Low Harmonic Drive
VLT HVAC Low Harmonic Drive Instruction
Manual
6-28
MG.16.A1.22 - VLT
®
is a registered Danfoss trademark
6