5-12 Terminal 27 Digital Input
Option:
Function:
[2] *
Coast inverse
Functions are described under 5-1*
Digital Inputs
5-13 Terminal 29 Digital Input
Option:
Function:
Select the function from the available digital input range and the additional options [60], [61], [63]
and [64]. Counters are used in Smart Logic Control functions. This parameter is available for the FC
302 only.
[14] *
Jog
Functions are described under 5-1*
Digital Inputs
5-14 Terminal 32 Digital Input
Option:
Function:
[0] *
No Operation
Same options and functions as par. 5-1*
Digital Inputs
, except for
Pulse input
.
5-15 Terminal 33 Digital Input
Option:
Function:
[0] *
No Operation
Same options and functions as par. 5-1*
Digital Inputs
.
5-40 Function Relay
Array [8]
(Relay 1 [0], Relay 2 [1]
Option MCB 105: Relay 7 [6], Relay 8 [7] and Relay 9 [8]).
Select options to define the function of the relays.
The selection of each mechanical relay is realized in an array parameter.
Option:
Function:
[0] *
No operation
[1]
Control ready
[2]
Unit ready
[4]
Enable / no warning
[5] *
Running
Default setting for relay 2.
[9] *
Alarm
Default setting for relay 1.
[10]
Alarm or warning
[12]
Current limit
[21]
Thermal warning
[22]
Ready,no thermal W
[24]
Ready, voltage OK
[26]
Bus OK
[122]
No alarm
[125]
Hand mode
[126]
Auto mode
6 How to Program the Low Harmonic Drive
VLT HVAC Low Harmonic Drive Instruction
Manual
6-24
MG.16.A1.22 - VLT
®
is a registered Danfoss trademark
6