Line Power Supply 3 x 525-690 V AC
FC 302
P37K
P45K
P55K
P75K
P90K
High/ Normal Load*
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
Typical shaft output at
690 V [kW]
37
45
45
55
55
75
75
90
90
110
Enclosure
IP21
D1
D1
D1
D1
D1
Enclosure IP54
D1
D1
D1
D1
D1
Enclosure
IP00
D2
D2
D2
D2
D2
Output current
Continuous
(at 690 V) [A]
46
54
54
73
73
86
86
108
108
131
Intermittent (60 sec
overload)
(at 690 V) [A]
74
59
86
80
117
95
129
119
162
144
Continuous KVA
(at 690 V) [KVA]
55
65
65
87
87
103
103
129
129
157
Max. input current
Continuous
(at 690 V) [A]
50
58
58
77
77
87
87
109
109
128
Max. cable size, line
power, motor, load
share and brake
[mm
2
(AWG)]
2x70 (2x2/0)
Max. external pre-
fuses [A]
1
125
160
200
200
250
Estimated power loss
at rated max. load [W]
4)
1355
1458
1459
1717
1721
1913
1913
2262
2264
2662
Weight,
enclosureIP21, IP 54
[kg]
96
Weight,
enclosureIP00 [kg]
82
Efficiency
4)
0.97
0.97
0.98
0.98
0.98
Output frequency
0-600 Hz
Heatsink overtemp.
trip
185°F [85°C]
Power card ambient
trip
140°F [60°C]
* High overload = 160% torque during 60 s, Normal overload = 110% torque during 60 s
VLT
®
Automation Drive FC 300
Instruction Manual High Power
5 General Specifications
MG.33.U2.22 - VLT
®
is a registered Danfoss trademark
5-9
5