Line Power Supply 3 x 525-690 V AC
FC 302
P110
P132
P160
P200
High/ Normal Load*
HO
NO
HO
NO
HO
NO
HO
NO
Typical shaft output at
550 V [kW]
90
110
110
132
132
160
160
200
Typical shaft output at
575 V [HP]
125
150
150
200
200
250
250
300
Typical shaft output at
690 V [kW]
110
132
132
160
160
200
200
250
Enclosure
IP21
D1
D1
D2
D2
Enclosure IP54
D1
D1
D2
D2
Enclosure
IP00
D3
D3
D4
D4
Output current
Continuous
(at 550 V) [A]
137
162
162
201
201
253
253
303
Intermittent (60 sec
overload)
(at 550 V) [A]
206
178
243
221
302
278
380
333
Continuous
(at 575/690 V) [A]
131
155
155
192
192
242
242
290
Intermittent (60 sec
overload)
(at 575/690 V) [A]
197
171
233
211
288
266
363
319
Continuous KVA
(at 550 V) [KVA]
131
154
154
191
191
241
241
289
Continuous KVA
(at 575 V) [KVA]
130
154
154
191
191
241
241
289
Continuous KVA
(at 690 V) [KVA]
157
185
185
229
229
289
289
347
Max. input current
Continuous
(at 550 V) [A]
130
158
158
198
198
245
245
299
Continuous
(at 575 V) [A]
124
151
151
189
189
234
234
286
Continuous
(at 690 V) [A]
128
155
155
197
197
240
240
296
Max. cable size, line pow-
er motor, load share and
brake [mm
2
(AWG)]
2 x 70 (2 x 2/0)
2 x 70 (2 x 2/0)
2 x 185 (2 x 350
mcm)
2 x 185 (2 x 350
mcm)
Max. external pre-fuses
[A]
1
315
350
350
400
Estimated power loss
at rated max. load [W]
4)
2664
3114
2953
3612
3451
4292
4275
5156
Weight,
enclosureIP21, IP 54 [kg]
96
104
125
136
Weight,
enclosureIP00 [kg]
82
91
112
123
Efficiency
4)
0.98
Output frequency
0-600 Hz
Heatsink overtemp. trip
185°F [85°C]
194°F [90°C]
230°F [110°C]
230°F [110°C]
Power card ambient trip
140°F [60°C]
* High overload = 160% torque during 60 s, Normal overload = 110% torque during 60 s
5 General Specifications
VLT
®
Automation Drive FC 300
Instruction Manual High Power
5-10
MG.33.U2.22 - VLT
®
is a registered Danfoss trademark
5