Line Power Supply 3 x 525-690 V AC
FC 302
P250
P315
P355
High/ Normal Load*
HO
NO
HO
NO
HO
NO
Typical shaft output at 550 V
[kW]
200
250
250
315
315
355
Typical shaft output at 575 V
[HP]
300
350
350
400
400
450
Typical shaft output at 690 V
[kW]
250
315
315
400
355
450
Enclosure
IP21
D2
D2
E1
Enclosure IP54
D2
D2
E1
Enclosure
IP00
D4
D4
E2
Output current
Continuous
(at 550 V) [A]
303
360
360
418
395
470
Intermittent (60 sec overload)
(at 550 V) [A]
455
396
540
460
593
517
Continuous
(at 575/690 V) [A]
290
344
344
400
380
450
Intermittent (60 sec overload)
(at 575/690 V) [A]
435
378
516
440
570
495
Continuous KVA
(at 550 V) [KVA]
289
343
343
398
376
448
Continuous KVA
(at 575 V) [KVA]
289
343
343
398
378
448
Continuous KVA
(at 690 V) [KVA]
347
411
411
478
454
538
Max. input current
Continuous
(at 550 V) [A]
299
355
355
408
381
453
Continuous
(at 575 V) [A]
286
339
339
390
366
434
Continuous
(at 690 V) [A]
296
352
352
400
366
434
Max. cable size, line power,
motor and load share [mm
2
(AWG)]
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
4 x 240
(4 x 500 mcm)
Max. cable size, brake [mm
2
(AWG)]
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
Max. external pre-fuses [A]
1
500
550
700
Estimated power loss
at rated max. load [W]
4)
4875
5821
5185
6149
5383
6449
Weight,
enclosureIP21, IP 54 [kg]
151
165
263
Weight,
enclosureIP00 [kg]
138
151
221
Efficiency
4)
0.98
Output frequency
0-600 Hz
0-500 Hz
0-500 Hz
Heatsink overtemp. trip
230°F [110°C]
230°F [110°C]
185°F [85°C]
Power card ambient trip
140°F [60°C]
140°F [60°C]
154°F [68°C]
* High overload = 160% torque during 60 s, Normal overload = 110% torque during 60 s
VLT
®
Automation Drive FC 300
Instruction Manual High Power
5 General Specifications
MG.33.U2.22 - VLT
®
is a registered Danfoss trademark
5-11
5