2.1.6 Safe Stop
The FC 302 can perform the safety function
Safe Torque Off
(As defined by draft CD IEC 61800-5-2) or
Stop Category 0
(as defined in EN 60204-1).
It is designed and deemed suitable for the requirements of Safety Category 3 in EN 954-1. This function is called safe stop. Prior to integrating and using
safe stop in an installation, a thorough risk analysis must be carried out on the installation in order to determine whether the safe stop functionality and
safety category are appropriate and sufficient. In order to install and use the Safe Stop function in accordance with the requirements of Safety Category
3 in EN 954-1, the related information and instructions of the FC 300 Design Guide MG.33.BX.YY must be followed! The information and instructions
contained in the Instruction Manual are not sufficient for a correct and safe use of the safe stop functionality!
2 Safety Instructions and General Warning
VLT
®
Automation Drive FC 300
Instruction Manual High Power
2-4
MG.33.U2.22 - VLT
®
is a registered Danfoss trademark
2