1-22 Motor Voltage
Range:
Function:
Size rela-
ted*
[10 - 1,000 V]
Enter the nominal motor voltage according to the motor nameplate data. The default value corre-
sponds to the nominal rated output of the unit.
This parameter cannot be adjusted while the motor is running.
1-23 Motor Frequency
Option:
Function:
Min - Max motor frequency: 20 - 1,000 Hz
Select the motor frequency value from the motor nameplate data. If a value different from 50 Hz
or 60 Hz is selected, it is necessary to adapt the load independent settings in par. 1-50 to 1-53. For
87 Hz operation with 230/400 V motors, set the nameplate data for 230 V/50 Hz. Adapt par. 4-13
Motor Speed High Limit [RPM)
and par. 3-03
Maximum Reference
to the 87 Hz application.
[50] *
50 Hz when parameter 0-03 = inter-
national
[60]
60 Hz when parameter 0-03 = US
1-24 Motor Current
Range:
Function:
Size rela-
ted*
[0.1 - 10,000 A]
Enter the nominal motor current value from the motor nameplate data. This data is used for cal-
culating motor torque, motor thermal protection, etc.
This parameter cannot be adjusted while the motor is running.
1-25 Motor Nominal Speed
Range:
Function:
Size rela-
ted*
[100 - 60,000 rpm]
Enter the nominal motor speed value from the motor nameplate data. This data is used for calcu-
lating automatic motor compensations.
This parameter cannot be adjusted while the motor is running.
5-12 Terminal 27 Digital Input
Option:
Function:
Select the function from the available digital input range.
No operation
[0]
Reset
[1]
Coast inverse
[2]
Coast and reset inverse
[3]
Quick stop inverse
[4]
DC brake inverse
[5]
Stop inverse
[6]
Start
[8]
Latched start
[9]
Reversing
[10]
Start reversing
[11]
Enable start forward
[12]
Enable start reverse
[13]
Jog
[14]
Preset ref bit 0
[16]
Preset ref bit 1
[17]
Preset ref bit 2
[18]
Freeze reference
[19]
Freeze output
[20]
Speed up
[21]
4 How to Program
VLT
®
Automation Drive FC 300
Instruction Manual High Power
4-4
MG.33.U2.22 - VLT
®
is a registered Danfoss trademark
4