Line Power Supply 3 x 525-690 V AC
FC 302
P630
P710
P800
P900
P1M0
High/ Normal Load*
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
Typical shaft output at
550 V [kW]
500
560
560
670
670
750
750
850
850
1000
Typical shaft output at
575 V [HP]
650
750
750
950
950
1050
1050
1150
1150
1350
Typical shaft output at
690 V [kW]
630
710
710
800
800
900
900
1000
1000
1200
Enclosure IP21, 54
without/with options
cabinet
F1/ F3
F1/ F3
F1/ F3
F2/ F4
F2/ F4
Output current
Continuous
(at 550 V) [A]
659
763
763
889
889
988
988
1108
1108
1317
Intermittent (60 sec
overload)
(at 550 V) [A]
989
839
1145
978
1334
1087
1482
1219
1662
1449
Continuous
(at 575/690 V) [A]
630
730
730
850
850
945
945
1060
1060
1260
Intermittent (60 sec
overload)
(at 575/690 V) [A]
945
803
1095
935
1275
1040
1418
1166
1590
1386
Continuous KVA
(at 550 V) [KVA]
628
727
727
847
847
941
941
1056
1056
1255
Continuous KVA
(at 575 V) [KVA]
627
727
727
847
847
941
941
1056
1056
1255
Continuous KVA
(at 690 V) [KVA]
753
872
872
1016
1016
1129
1129
1267
1267
1506
Max. input current
Continuous
(at 550 V) [A]
642
743
743
866
866
962
962
1079
1079
1282
Continuous
(at 575 V) [A]
613
711
711
828
828
920
920
1032
1032
1227
Continuous
(at 690 V) [A]
613
711
711
828
828
920
920
1032
1032
1227
Max. cable size,motor
[mm
2
(AWG
2)
)]
8x150
(8x300 mcm)
12x150
(12x300 mcm)
Max. cable size, line
power [mm
2
(AWG
2)
)]
8x240
(8x500 mcm)
Max. cable size, load
sharing [mm
2
(AWG
2)
)]
4x120
(4x250 mcm)
Max. cable size, brake
[mm
2
(AWG
2)
)
4x185
(4x350 mcm)
6x185
(6x350 mcm)
Max. external pre-
fuses [A]
1
1600
2000
Estimated power loss
at rated max. load [W]
4)
Weight,
enclosureIP21, IP 54
[kg]
1004/ 1299
1004/ 1299
1004/ 1299
1246/ 1541
1246/ 1541
Weight, Rectifier Mod-
ule [kg]
102
102
102
136
136
Weight, Inverter Mod-
ule [kg]
102
102
136
102
102
Efficiency
4)
0.98
Output frequency
0-500 Hz
Heatsink overtemp.
trip
Power card ambient
trip
* High overload = 160% torque during 60 s, Normal overload = 110% torque during 60 s
VLT
®
Automation Drive FC 300
Instruction Manual High Power
5 General Specifications
MG.33.U2.22 - VLT
®
is a registered Danfoss trademark
5-13
5