3.7.3 Speed Up/Down
Terminals 29/32 = Speed up/down: .
Terminal 18 = Par. 5-10 [9]
Start
(default)
Terminal 27 = Par. 5-12 [19]
Freeze reference
Terminal 29 = Par. 5-13 [21]
Speed up
Terminal 32 = Par. 5-14 [22]
Slow
Note: Terminal 29 only in FC x02 (x=series type).
3.7.4 Potentiometer Reference
Voltage reference via a potentiometer:
Reference Source 1 = [1]
Analog input 53
(default)
Terminal 53, Low Voltage = 0 Volt
Terminal 53, High Voltage = 10 Volt
Terminal 53, Low Ref./Feedback = 0 RPM
Terminal 53, High Ref./Feedback = 1500 RPM
Switch S201 = OFF (U)
3 How to Install
VLT
®
Automation Drive FC 300
Instruction Manual High Power
3-58
MG.33.U2.22 - VLT
®
is a registered Danfoss trademark