Term. no.
96
97
98
99
U
V
W
PE
1)
Motor voltage 0–100% of AC line voltage.
3 wires out of motor
U1
V1
W1
PE
1)
Delta-connected
W2
U2
V2
6 wires out of motor
U1
V1
W1
PE
1)
Star-connected U2, V2, W2
U2, V2 and W2 to be interconnected separately.
1)
Protected Ground Connection
NOTE!
In motors without phase insulation paper or other in-
sulation reinforcement suitable for operation with volt-
age supply (such as an adjustable frequency drive), fit
a sine-wave filter on the output of the adjustable fre-
quency drive.
Figure 3.32: Compact IP 21 (NEMA 1) and IP 54 (NEMA 12), enclosure D1
VLT
®
Automation Drive FC 300
Instruction Manual High Power
3 How to Install
MG.33.U2.22 - VLT
®
is a registered Danfoss trademark
3-37
3