Line Power Supply 3 x 380-500 V AC
FC 302
P450
P500
P560
P630
P710
P800
High/ Normal Load*
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
Typical shaft output at
400 V [kW]
450
500
500
560
560
630
630
710
710
800
800
1000
Typical shaft output at
460 V [HP]
600
650
650
750
750
900
900
1000 1000 1200 1200 1350
Typical shaft output at
500 V [kW]
530
560
560
630
630
710
710
800
800
1000 1000 1100
Enclosure IP21, 54
without/with options
cabinet
F1/ F3
F1/ F3
F1/ F3
F1/ F3
F2/ F4
F2/ F4
Output current
Continuous
(at 400 V) [A]
800
880
880
990
990
1120 1120 1260 1260 1460 1460 1720
Intermittent (60 sec
overload)
(at 400 V) [A]
1200
968
1320
1089 1485 1232 1680 1386 1890 1606 2190 1892
Continuous
(at 460/500 V) [A]
730
780
780
890
890
1050 1050 1160 1160 1380 1380 1530
Intermittent (60 sec
overload)
(at 460/500 V) [A]
1095
858
1170
979
1335 1155 1575 1276 1740 1518 2070 1683
Continuous KVA
(at 400 V) [KVA]
554
610
610
686
686
776
776
873
873
1012 1012 1192
Continuous KVA
(at 460 V) [KVA]
582
621
621
709
709
837
837
924
924
1100 1100 1219
Continuous KVA
(at 500 V) [KVA]
632
675
675
771
771
909
909
1005 1005 1195 1195 1325
Max. input current
Continuous
(at 400 V) [A]
779
857
857
964
964
1090 1090 1227 1227 1422 1422 1675
Continuous (at
460/500 V) [A]
711
759
759
867
867
1022 1022 1129 1129 1344 1344 1490
Max. cable size,motor
[mm
2
(AWG
2)
)]
8x150
(8x300 mcm)
12x150
(12x300 mcm)
Max. cable size, line
power [mm
2
(AWG
2)
)]
8x240
(8x500 mcm)
Max. cable size, load
sharing [mm
2
(AWG
2)
)]
4x120
(4x250 mcm)
Max. cable size, brake
[mm
2
(AWG
2)
)
4x185
(4x350 mcm)
6x185
(6x350 mcm)
Max. external pre-
fuses [A]
1
1600
2000
2500
Estimated power loss
at rated max. load [W]
4)
Weight,
enclosureIP21, IP 54
[kg]
1004/ 1299
1004/ 1299
1004/ 1299
1004/ 1299
1246/ 1541
1246/ 1541
Weight Rectifier Mod-
ule [kg]
102
102
102
102
136
136
Weight Inverter Mod-
ule [kg]
102
102
102
136
102
102
Efficiency
4)
0.98
Output frequency
0-600 Hz
Heatsink overtemp.
trip
Power card ambient
trip
* High overload = 160% torque during 60 s, Normal overload = 110% torque during 60 s
5 General Specifications
VLT
®
Automation Drive FC 300
Instruction Manual High Power
5-8
MG.33.U2.22 - VLT
®
is a registered Danfoss trademark
5