017
Local reset of trip (LOCAL RESET)
Value:
Not possible (DISABLE)
[0]
Possible (ENABLE)
[1]
Function:
In this parameter, the reset function can be selected/
removed from the keyboard.
This key can be used when parameter 002 has been
set for
Remote control
[0] or
Local control
[1].
Description of choice:
If
Disable
[0] is selected in this parameter, the [RESET]
key will be inactive.
NOTE
Only select
Disable
[0] if an external reset
signal has been connected via the digital
inputs.
018
Lock for data change
(DATA CHANGE LOCK)
Value:
Not locked (NOT LOCKED)
[0]
Locked (LOCKED)
[1]
Function:
In this parameter, the software can "lock" the control,
which means that data changes cannot be made via
LCP (however, this is still possible via the serial com-
munication port).
Description of choice:
If
Locked
[1] is selected, data changes cannot be
made.
019
Operating state at Power up, local con-
trol
(POWER UP ACTION)
Value:
Auto restart, use saved ref. (AUTO RE-
START)
[0]
Forced stop, use saved ref. (LOCAL=STOP)
[1]
Forced stop, set ref. to 0
(LOCAL=STOP, REF=0)
[2]
Function:
Setting of the operating mode when the mains voltage
is reconnected.
This function can only be active in connection with
Local control
[1] in parameter 002.
Description of choice:
Auto restart, use saved ref.
[0] is selected if the unit is
to start up with the same local reference (set in pa-
rameter 003) and the same start/stop conditions (given
via the [START/STOP] keys) that the adjustable fre-
quency drive had before it was switched off.
Forced stop, use saved ref.
[1] is used if the unit is to
remain stopped when the mains voltage is connected,
until the [START] key is pressed. After the start com-
mand, the local reference used is set in parameter 003.
Forced stop, set ref. to 0
[2] is selected if the unit is to
remain stopped when the mains voltage is connected.
Local reference (parameter 003) is reset.
NOTE
In remote controlled operation (parameter
002), the start/stop condition at power up
will depend on the external control sig-
nals. If
Pulse start
[2] is selected in param-
eter 302, the motor will remain stopped at
power-up.
027
Warning readout line
(WARNING READOUT)
Value:
Warning in line 1/2
[0]
Warning in line 3/4
[1]
VLT
®
5000 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
85
Progra
mming
Содержание VLT 5000 Series
Страница 2: ...VLT 5000 Instruction Manual ...
Страница 3: ......
Страница 45: ...Mechanical dimensions cont VLT 5000 Series 42 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Страница 196: ...RELATIVE VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 193 List of functions ...
Страница 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 198: ...References VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 195 List of functions ...
Страница 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Страница 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 238: ...Rev 2006 12 12 www danfoss com drives 175R5271 MG51C522 MG51C522 MG51C522 VLT 5000 Instruction Manual ...
Страница 239: ......