Factory Settings
PNU
Parameter
Factory setting
Range
Changes
4-Setup
Conversion
Data
#
description
during operation
index
type
001
Language
English
Yes
No
0
5
002
Local/remote control
Remote control
Yes
Yes
0
5
003
Local reference
000.000
Yes
Yes
-3
4
004
Active setup
Setup 1
Yes
No
0
5
005
Programming setup
Active setup
Yes
No
0
5
006
Copying of setups
No copying
No
No
0
5
007
LCP copy
No copying
No
No
0
5
008
Display scaling of motor frequency 1
0.01 - 500.00
Yes
Yes
-2
6
009
Display linie 2
Frequency [Hz]
Yes
Yes
0
5
010
Display line 1.1
Reference [%]
Yes
Yes
0
5
011
Display line 1.2
Motor current [A]
Yes
Yes
0
5
012
Display line 1.3
Power [kW]
Yes
Yes
0
5
013
Local control/configura
LCP digital control/as
par.100
Yes
Yes
0
5
014
Local stop
Possible
Yes
Yes
0
5
015
Local jog
Not possible
Yes
Yes
0
5
016
Local reversing
Not possible
Yes
Yes
0
5
017
Local reset of trip
Possible
Yes
Yes
0
5
018
Lock for data change
Not locked
Yes
Yes
0
5
019
Operating state at power-up, local
control
Forced stop, use
saved ref.
Yes
Yes
0
5
027
Warning readout
Warning in line 1/2
Yes
No
0
5
Changes during operation:
"Yes" means that the parameter can be changed,
while the adjustable frequency drive is in operation.
"No" means that the adjustable frequency drive must
be stopped before a change can be made.
4-Setup:
"Yes" means that the parameter can be programmed
individually in each of the four setups, i.e. the same
parameter can have four different data values. "No"
means that the data value will be the same in all four
setups.
Conversion index:
This number refers to a conversion figure to be used
when writing or reading by means of an adjustable fre-
quency drive.
Conversion index
Conversion factor
74
0.1
2
100
1
10
0
1
-1
0.1
-2
0.01
-3
0.001
-4
0.0001
Data type:
Data type shows the type and length of the telegram.
Data type
Description
3
Integer 16
4
Integer 32
5
Unsigned 8
6
Unsigned 16
7
Unsigned 32
9
Text string
VLT
®
5000 Series
220
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
Содержание VLT 5000 Series
Страница 2: ...VLT 5000 Instruction Manual ...
Страница 3: ......
Страница 45: ...Mechanical dimensions cont VLT 5000 Series 42 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Страница 196: ...RELATIVE VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 193 List of functions ...
Страница 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 198: ...References VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 195 List of functions ...
Страница 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Страница 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Страница 238: ...Rev 2006 12 12 www danfoss com drives 175R5271 MG51C522 MG51C522 MG51C522 VLT 5000 Instruction Manual ...
Страница 239: ......